1500V, Test, measurement or monitoring equipment for protection test section 9: insulation fault
positioning equipment for IT systems
;
◆
JGJ 16-2008
Code for electrical design of civil buildings
;
◆
IEC61558-1: 2009
Safety of power transformers, power supplies, reactors and similar products
section 1: General requirements and tests
;
◆
IEC61558-2-15: 2011
Safety of power transformers, power supplies and similar products section
16:
Special requirements for isolation transformers for power supply in medical locations
.
4 Technical parameters
4.1 Technical parameters of AITR series medical isolation transformer
Refer to Table 3.
Table 3 Technical Parameters of AITR Series of Medical Isolation Transformer
Type
AITR10000
AITR8000
AITR6300
AITR5000
AITR3150
Insulation
class
H
H
H
H
H
Protection
class
IP00
IP00
IP00
IP00
IP00
Power / voltage
/ current
Rated power
10000VA
8000VA
6300VA
5000VA
3150VA
Rated frequency 50-60Hz
50-60Hz
50-60Hz
50-60Hz
50-60Hz
Rated
input
voltage
AC230V
AC230V
AC230V
AC230V
AC230V
Rated
input
current
45.3A
36A
28.5A
22.5
14.2A
Rated
output
voltage
AC230V/115V AC230V/115V
AC230V/115V
AC230V/115V
AC230V/115V
Rated
output
current
43.5A
34.7A
27.4A
21.7
13.7A
Inrush current
<12In
<12In
<12In
<12In
<12In
Leakage current <200μA
<200μA
<200μA
<200μA
<200μA
No load
input
current
1.359A
1.08A
0.855A
0.675A
0.426A
No load output
voltage
235V±3%
235V±3%
235V±3%
235V±3%
235V±3%
Short circuit
voltage
<6.9V
<6.9V
<6.9V
<6.9V
<7.5V
General