Q6SE-X60 Charging Chart-Cooling
200
220
240
260
280
300
320
340
360
380
400
420
440
460
480
500
520
540
560
580
600
75
80
85
90
95
100
105
110
115
120
125
130
135
Liquid Pressure
(psig)
Liquid Temperature (
° F)
Remove refrigerant when above curve
Add refrigerant when below curve
Figure 14. charging chart for 5 ton units
table 6. blower curves
moDEl
numbEr
Q6SE
motor
SPEED
taP
ExtErnal Static PrESSurE DroP
(incHES WatEr column)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
X36
Tap T1
1137
25.01
1075 26.45 1012 28.10
950
29.93
863
32.95
770
36.93
694
40.97
619
45.94
Tap T2**
1242
22.89
1187 23.95 1128 25.21 1057 26.90
993
28.63
921
30.87
827
34.38
754
37.71
Tap T3*
1418
20.05
1370 20.76 1308 21.74 1251 22.73 1204 23.62 1123 25.32 1064 26.72
974
29.19
Tap T4
1567
18.15
1515 18.77 1459 19.49 1397 20.35 1338 21.25 1272 22.35 1184 24.02 1107 25.69
Tap T5
1700
16.73
1658 17.15 1596 17.82 1534 18.54 1481 19.20 1421 20.01 1358 20.94 1279 22.23
X48
Tap T1
952
29.87
901
31.56
864
32.91
728
39.06
672
42.31
583
48.77
508
55.97
-
-
Tap T2**
1646
17.27
1593 17.85 1520 18.71 1476 19.26 1417 20.07 1349 21.08 1265 22.48 1198 23.73
Tap T3*
1764
16.12
1705 16.68 1626 17.49 1570 18.11 1525 18.65 1451 19.60 1403 20.27 1304 21.81
Tap T4
1962
14.49
1916 14.84 1838 15.47 1787 15.91 1720 16.53 1670 17.03 1595 17.83 1537 18.50
Tap T5
2391
11.89
2334 12.18 2301 12.36 2242 12.68 2180 13.04 2132 13.34 2074 13.71 2017 14.10
X60
Tap T1
1088
26.13
1032 27.55
958
29.68
878
32.39
789
36.04
715
39.77
641
44.36
570
49.89
Tap T2**
1764
16.12
1705 16.68 1626 17.49 1570 18.11 1525 18.65 1451 19.60 1403 20.27 1304 21.81
Tap T3*
1777
16.00
1736 16.38 1680 16.93 1634 17.40 1571 18.10 1513 18.79 1447 19.65 1382 20.57
Tap T4
2106
13.50
2059 13.81 2000 14.22 1944 14.63 1878 15.14 1828 15.55 1751 16.24 1689 16.84
Tap T5
2391
11.89
2334 12.18 2301 12.36 2242 12.68 2180 13.04 2132 13.34 2074 13.71 2017 14.10
* Denotes factory set cooling speed
** Denotes factory set electric heating speed
NOTE
: Airflow performance is with a dry coil
airflow Data