USER SETTINGS CHART CONTINUED
ALERT/ALARM CONFIGURATION SCREEN
Outlet Temp.
Setpoint Min. Limit
35 to 180
o
F
110
o
F
If setpoint is set below this value, an alert will
result.
Outlet Temp.
Setpoint
60 to 180
o
F
120
o
F
N/A
Configure at Valve Settings Menu, above
Outlet Temp.
Low Limit
-15 to -1
o
F
-7
o
F
If the outlet temp drops below the setpoint by
this value, an alarm will result.(2)(3)
Outlet Temp.
Low Limit
1 to 15
o
F
7
o
F
If the outlet temp goes above the setpoint by
this value, an alarm will result.(2)(3)
SANITIZATION SCREEN
Sanitization Setpoint
60 to 180
o
F
120
o
F
Setpoint changes after safe start confimation
Sanitization Time
.1 to 24 hours
.1 hours
At the end of the Sanitization Time, outlet temp.
setpoint will return to previous setting
PUMP CONTROL AND DATA SCREEN
Acceptable recirc.
Loop Setting Min.
60 to 180o F
90° F
If the return temp. goes below this value an alert
will result (2)
Acceptable recirc.
Loop Setting Max.
60 to 180o F
130° F
If the return temp. goes above this value an alert
will result (2)
Recirc Loop Setpoint
70 to 160o F
120° F
If the recirc loop is at or above this temp., the
pump control relay will deactivate (4)
Deadband
1 to 15o F
3° F
After a pump relay deactivation, the return temp.
must drop by this value before the relay reacti-
vates.
Temperature
Feedback
Return Sensor
(checked) or
unchecked
Return Sensor
Users that order a Final Fixture sensor will use
that sensor for the pump control relay (5)
Customization for Automatically Alternating Recirculation Pumps
(CONTACT ACORN FOR AVAILABILITY AND ADDITIONAL INFORMATION)
Pump Make and Model:
Pump Alternating
Cycle
7, 30, 60
or 90 days
7 days
Pump control signal will alternative between
control relays
Initiate Pump
Alternation
Off or On
Off
N/A
If initiated, cycle for next alternation will restart
(1) If factory configured, the factory-set values will be entered here. If the user is configuring the system on startup, please enter the selected valves in this column.
(2) To simultaneously activate an email or text alert notification, check the appropriate box. IMPORTANT NOTE: To be able to send email notifications, BASYC™
must be connected to a mail server, typically via the Ethernet LAN adapters included with every BASyC™ system.
(3) An alarm for this parameter will result in a relay output. A common relay output is provided for alarms, another common relay output for alerts. If other
configurations are required, please contact Acorn for a quotation.
(4) This capability eliminates any requirements for an AquaStat. On systems that are intended to operating with a constantly recirculating pump, it is recommended
that this be used as a pump shut off in the event of an emergency, high temperature, condition.
(5) A Return Sensor is most common for the Pump Relay function. But if so equipped, a Final Fixture sensor is a more efficient option for pump relay control, plus it
confirms that all fixtures on the system are at a desired LTHW temperature, a very critical point of data for bather safety and satisfaction.