Operation
6.2 Description of evaluation device front wall
Description
Table
A
: Possible displays
Display
Lights
Explanation
Water
Grease
Air
off
green
red
exists
exists
exists
LED 4
LED 3
LED 2
LED 1
Table
B
:
Button
Description
Test button 1
Output relay 1 is switched, half level signal can be
checked at ZLT (central technical supervision).
Test button 2
Output relay 2 is switched, full level signal can be
checked at ZLT (central technical supervision).
LED 4
LED 3
LED 2
LED 1
Test button H
Test button L
6.3 Condition description: Half level signal = 50 % of max. grease storage capacity
Condition in separator
Evaluation at evaluation device
Table
C
: Half level signal=50% max. grease storage cap.
Display
Lights
Sensors
Water
Grease
off
green
red
exists
exists
LED 4
LED 3
LED 2
LED 1
By pressing test button 1, this condition
can be simulated and tested at the ZLT
prior to reaching the condition.
The 2 upper sensors are covered with grease
50 % of max. grease layer
Sensors
6.4 Condition description: Full level signal = 80 % of max. grease storage capacity
Condition in separator
Evaluation at evaluation device
Table
D
: Full level signal=80% max. grease storage cap.
Display
Lights
Sensors
Water
Grease
off
green
red
exists
exists
LED 4
LED 3
LED 2
LED 1
By pressing test button 2, this condition
can be simulated and tested at the ZLT
prior to reaching the condition.
The 4 upper sensors are covered with grease.
>
80 % of max. grease layer
Sensors
GREASE-LEVEL-CONTROLLER
NOTICE
NOTICE