POMPE SOLUBLOC 2V
SOLUBLOC 2V PUMP
1.
SYMBOLS MEANINGS USED HEREIN
DANGER
Risk of electrocution.
DANGER
Risk of personal injury.
ATTENTION
Risk of pump and system deterioration.
2.
GENERAL SAFETY INSTRUCTIONS
The instructions listed below are purely indicative and in no way limited. The pump must always
be handled with the most care.
▪ The pump was designed for use in a closed circuit, in clean water at a temperature of more than +5 to 50° C.
▪ Do not modify the pump in any way; the guarantee will automatically be invalidated in the event of a pump
modification.
▪ For all repair work, only use spare parts supplied by the manufacturer; the latter will not be held liable in the event
of damage caused by the use of non original spare parts or parts which have been modified without prior approval of
the manufacturer.
▪ The safety and correct operation of the pump are guaranteed only if all the installation and commissioning
instructions have been followed.
▪ The pump must be installed in compliance with the applicable standards in force in the country of installation and
use, especially HD 384.7.702; we recommend you contact a professional for the pump installation.
▪ Cut off the electricity supply to the pump prior to any intervention.
▪ The limits specified in the technical data table must never be exceeded under any circumstances.
▪ In the event of a malfunction or failure, please contact your nearest manufacturer’s representative or the
manufacturer’s Technical Support Service.
▪ Hot surface in the area around the motor
.
3.
INSTALLATION AND STARTING UP
▪ Never operate the pump without any water.
▪ To ensure the correct operation of the pump:
- The pump must be installed horizontally and secured in place.
▪ Its performance is optimized if the pump is positioned below the water level.
▪ If the pump has to be installed above the water level, the height must not exceed 1,5 m and the length of the suction
pipe will have to be as short as possible in order to avoid significant suction times and pressure losses.
▪ For the correct air circulation and to ensure effective cooling, the fan grid must be located more than 30cm from a
wall.
3.1
ELECTRIC CONNECTIONS
▪ Make sure the electricity supply voltage and frequency correspond to the values specified on the pump data plate.
▪ The pump’s electrical system must be fitted with a differential guard with a value of no more than 30mA.
▪ When wiring the pump motor terminal board, make sure the electrical terminals are tightened properly and make
the earthing connection correctly.
▪ Check that the adjustment of the thermal relay in the electrical cabinet matches the pump motor intensity in order
to ensure the effective protection of the latter (see the pump data plate).
▪ Vérifier que le réglage du relais thermique de l’armoire électrique soit adaptée à l’intensité du moteur de la pompe
afin d’assurer une protection efficace de celui-ci (voir la plaque de la pompe).