Configuration and cabling
9
ADIP
Installation Guide
System
description
Installation
parameters
Events
Accessories
Configuration
and cabling
Tables
Data
Compatible
elements
Functions
description
Delete
Supervision
Reader
Connexion
nº2
The reader can be powered by the + and -
Vout
terminals (12v DC - 500mA max).
The controller can receive the reader in
Wiegand or Clock & Data formats via the W0-
CK and W1-DT terminals.
Fresh out of the factory:
The IN4 (PB2) input - C is dedicated to the
door control (relay 2) by pushbutton normally
open when it is not in use.
The IN5 (G2) input - C is dedicated to the
supervision of the door by normally closed
magnetic contact.
The IN6 (I2) input - C is dedicated to the read-
ing by sensor, normally open when it is not in
use. When the sensor switches to the nor-
mally closed state, the reading is no longer
possible.
W1
DT
Vout
-
+
G2
IN5
I2
IN6
C
PB2
IN4
W0
CK
Door relay 1
The relay N ° 1 is a programmable relay 5A
under 30Vdc, dedicated to door control 1 as
it left the factory.
It can be controlled by time range, input func-
tion, by badge, PB-1 push putton input. It can
operate in timed mode, on - off or tracking of
an input.
NC NO C NC
RL1
Door relay 2
The relay N ° 2 is a programmable relay 5A
under 30Vdc, dedicated to door control 2 as
it left the factory.
It can be controlled by time range, input func-
tion, by badge, PB-2 push putton input. It can
operate in timed mode, on - off or tracking of
an input.
NC NO C NC
RL1
Optional
relay 3
The relay N° 3 is a programmable relay 5A at
30Vdc.
It can be controlled by time range, input func-
tion, by badge. It can operate in timed mode,
on - off or tracking of an input.
NC NO C NC
RL1
Optional
relay 4
The relay N° 4 is a 5A programmable relay at
30Vdc.
It can be controlled by time range, input func-
tion, by badge. It can operate in timed mode,
on - off or tracking of an input.
NC NO C NC
RL1
Connector
RJ45
RJ45 female connector dedicated to local or
remote communication with a computer or
with the ADIP network.
Connector
RJ45
RJ45 female connector dedicated to local or
remote communication with a computer or
with the ADIP network.
Battery
Type CR2032 for maintaining the calendar
Programma-
tion bridge
Performs NEXT procedures:
- Recover factory passwords
- DHCP Addressing
- Reset Factory
N P
Red warming
light
Indicates the different configuration phases
DL1