PRODUCT SPECIFICATIONS

Supply Voltage:

4 to 20 mA Output:

 250Ω Load: 18 to 36 VDC  |  

500Ω Load:

 20 to 36VDC | 

0 to 5 / 0 to 10 VDC Output:

 16 to 36 VDC, 21.6 to 26.4 VAC, 50/60 Hz

Supply Current:

4-20 mA Output:

 24 mA minimum 

0-5 VDC  |  0-10 VDC Outputs:

 6 mA maximum

Output Signals:

2-wire:

 Linear 4-20 mA DC Current (field selectable)  |  

3-wire: 

0-5 VDC; 0-10 VDC 

(default)

Response Time (0-100% FSO):

8 seconds

Output Update Rate:

1 second

Output Load Resistance:

4 to 20 mA:

 500 ohms maximum  |  

0-5 VDC/0-10 VDC: 

5K ohms minimum

Warm Up Time:

15 minutes (wait 15 minutes before zeroing)

Operating Temperature:

Transducer:

 -40-257°F (-40-125°C)  | 

 Electronics/Housing/Cables:

 32-167°F 

(0-75°C)

Compensated Temperature Range:

32 to 140°F (0 to 60°C)

Storage Temperature:

-13 to 176ºF (-25 to 80ºC)

Operating Humidity:

10 to 90% RH non-condensing

Proof Pressure:

A/WPR2-30 Series

 and 

A/WPR2-100 Series:

 3X FS  |  

A/WPR2-300 Series: 

2X FS

Burst Pressure:

1500 psi

Media Types:

Any liquids or gases compatible with Neoprene seal

Process Fitting Material:

304 SS

Process Fitting Size:

1/4"-18 NPT Male; Pressure Snubber included for light oils/water

Transducer Cable Rating 

|

 Connector 

Type:

Type CMP – Plenum Rated (UL Standard 444), NEC Article 800  |  Packard Connector

Metal Clad Rating:

Continuously interlocked Type 304 stainless steel core

Enclosure Rating:

NEMA 4X/IP66

Recommended Torque Specification:

150 in lbs (16.95 Nm)

WARRANTY

The ACI WPR2 Series is covered by ACI’s Five (5) Year Limited Warranty, which is located in the front of ACI’S 

SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s web site: 

www.workaci.com.

W.E.E.E. DIRECTIVE 

At the end of their useful life the packaging and product should be disposed of via a suitable recycling 

centre. Do not dispose of with household waste. Do not burn.

Summary of Contents for WPR2 Series

Page 1: ...d on a ceramic capacitive sensing element with 18 NPT male 304 stainless steel fittings The WPR2 s enclosure opens conveniently to allow it to be reconfigured between three additional ranges and outpu...

Page 2: ...r use the dimensions listed in FIGURE 1 p 1 to measure out Output Signal SW8 Output Mode SW7 Position 2 Supply Voltage Wire Connection Vout 0 5 VDC 5V VAC VDC V COM VOUT Vout 0 10 VDC 10V VAC VDC V CO...

Page 3: ...ared transformer If the 24 VDC or 24VAC power is shared with devices that have coils such as relays solenoids or other inductors each coil must have an MOV DC AC Transorb Transient Voltage Suppressor...

Page 4: ...he corresponding terminal block inside the housing Otherwise ACI will not guarantee the accuracy specifications DO NOT REPLACE SENSORS WITH ANY OTHER SENSORS THEWPR2 UNITS ARE CALIBRATEDWITHTHE HIGH A...

Page 5: ...2 1 2 3 4 5 ON BI 5V BAR A 1 UNI 10V PSI B 2 1 2 3 4 5 ON BI 5V BAR A 1 UNI 10V PSI B 2 1 2 3 4 5 ON BI 5V BAR A 1 UNI 10V PSI B 2 1 2 3 4 5 ON BI 5V BAR A 1 UNI 10V PSI B 2 1 2 3 4 5 ON BI 5V BAR A...

Page 6: ...able for pressures over 100 PSI Verify the HIGH Sensor Voltage is between 0 5 VDC 0 PSI and 4 5 VDC Max Line Pressure When measuring from the HIGH Sensor terminal block GND Black Wire to OUT White Wir...

Page 7: ...60 C Storage Temperature 13 to 176 F 25 to 80 C Operating Humidity 10 to 90 RH non condensing Proof Pressure A WPR2 30 Series and A WPR2 100 Series 3X FS A WPR2 300 Series 2X FS Burst Pressure 1500 p...

Page 8: ...Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 8 Version 22 0 I0000756...

Reviews: