WPR2

VFD

WIRING INSTRUCTIONS 

PRECAUTIONS

• 

Remove power before wiring. Never connect or disconnect wiring with power applied.

• 

When using a shielded cable, ground the shield only at the controller end. Grounding both 

ends can cause a ground loop.

• 

It is recommended you use an isolated UL-listed class 2 transformer when powering the unit 

with 24 VAC. Failure to wire the devices with the correct polarity when sharing transformers 

may result in damage to any device powered by the shared transformer.

• 

If the 24 VDC or 24VAC power is shared with devices that have coils such as relays, solenoids, 

or other inductors, each coil must have an MOV, DC/AC Transorb, Transient Voltage 

Suppressor (ACI Part: 142583), or diode placed across the coil or inductor. The cathode, or 

banded side of the DC Transorb or diode, connects to the positive side of the power supply. 

Without these snubbers, coils produce very large voltage spikes when de-energizing that 

can cause malfunction or destruction of electronic circuits.

Open the cover of the enclosure. ACI recommends 

16 to 26 AWG twisted pair wires or shielded cable 

for all transmitters. Twisted pair may be used for 

2-wire current output transmitters or 3-wire for 

voltage output. All wiring must comply with local 

and National Electric Codes. After wiring, close the 

cover.

Summary of Contents for WPR2 Series

Page 1: ...d on a ceramic capacitive sensing element with 18 NPT male 304 stainless steel fittings The WPR2 s enclosure opens conveniently to allow it to be reconfigured between three additional ranges and outpu...

Page 2: ...r use the dimensions listed in FIGURE 1 p 1 to measure out Output Signal SW8 Output Mode SW7 Position 2 Supply Voltage Wire Connection Vout 0 5 VDC 5V VAC VDC V COM VOUT Vout 0 10 VDC 10V VAC VDC V CO...

Page 3: ...ared transformer If the 24 VDC or 24VAC power is shared with devices that have coils such as relays solenoids or other inductors each coil must have an MOV DC AC Transorb Transient Voltage Suppressor...

Page 4: ...he corresponding terminal block inside the housing Otherwise ACI will not guarantee the accuracy specifications DO NOT REPLACE SENSORS WITH ANY OTHER SENSORS THEWPR2 UNITS ARE CALIBRATEDWITHTHE HIGH A...

Page 5: ...2 1 2 3 4 5 ON BI 5V BAR A 1 UNI 10V PSI B 2 1 2 3 4 5 ON BI 5V BAR A 1 UNI 10V PSI B 2 1 2 3 4 5 ON BI 5V BAR A 1 UNI 10V PSI B 2 1 2 3 4 5 ON BI 5V BAR A 1 UNI 10V PSI B 2 1 2 3 4 5 ON BI 5V BAR A...

Page 6: ...able for pressures over 100 PSI Verify the HIGH Sensor Voltage is between 0 5 VDC 0 PSI and 4 5 VDC Max Line Pressure When measuring from the HIGH Sensor terminal block GND Black Wire to OUT White Wir...

Page 7: ...60 C Storage Temperature 13 to 176 F 25 to 80 C Operating Humidity 10 to 90 RH non condensing Proof Pressure A WPR2 30 Series and A WPR2 100 Series 3X FS A WPR2 300 Series 2X FS Burst Pressure 1500 p...

Page 8: ...Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Page 8 Version 22 0 I0000756...

Reviews: