MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562
Page 6 of 33
www.workaci.com
(888) 967-5224
b.
Network Setup for Transceiver Configuration
•
A network connection using a crossover cable is required during the initial setup of the
Transceiver for transporting the Transceiver Configuration File via FTP.
•
Connect the MOD9200 Transceiver (J2) to a 10/100Base-T Ethernet network or use a
crossover cable to connect directly to the PC.
•
Apply 24 VAC 60 Hz power to the MOD9200 Transceiver.
c.
Setting A New IP Address
•
The MOD9200 is shipped from the factory with an IP address of 192.168.0.1 and a
subnet mask of 255.255.255.0 .
Note:
To initially connect to the Transceiver the networked PC must have a static IP
address in the form of 192.168.0.X where X is > 2 with a subnet mask of
255.255.255.0.
•
The IP Address can be changed by changing the IP Address in the Transceiver Config
File. Open either an existing config file or a new config file using the ACI Programmer
Software.
•
Click on Settings > TCP/IP Transport.
•
Enter the new IP Address and Subnet Mask and click OK. The new IP Address will take
affect when the Config File is downloaded to the Transceiver. Please note the “Router
Setup-Webserver Only” window is not used by the MOD9200.