MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562
Page 26 of 33
www.workaci.com
(888) 967-5224
•
Click on “Connect” and the status of the connection will be displayed in the Comm
Status window. When the Transceiver is connected click on “Send File” to the send the
config file to the Transceiver.
l.
Activating The Config File
•
Once the config file has been sent to the Transceiver it will become active immediately.
If you have changed the IP Address in the config file you will lose your connection and
have to reconnect using the IP Address and Subnet Mask that was sent in the
new config
file
.
•
To confirm that the appropriate configuration file is saved on the Transceiver – reopen
the File Transfer Dialog and click on “Get File” to retrieve a copy of the active
configuration file from the Transceiver. The Editor will automatically save this file in the
folder “trs” with the file name of “ _config.ini”.
•
Click on File > Open Config File and select the “_config.ini” file. Click on “Open” to
open the file in the Editor. Confirm that the file is the same as the original configuration
file. Since the “Group Name” and the “Point Name” fields are not used by the
MOD9200 transceiver, these fields will now be blank. All the other fields and settings
should be the same as the original ,ini file.