MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562
Page 31 of 33
www.workaci.com
(888) 967-5224
b.
Installing the FTT-10 Network
1.
Choose a location close to the LonWorks® network connection and away from the
ground.
2.
Mount the Transceiver on the wall using four #8 screws.
3.
24 VAC Input - Connect 24VAC 60 Hz and earth ground to the input terminals using
20 AWG wire as shown in the product data sheet.
4.
FTT-10 - Use 20 or 22 gauge shielded twisted pair wire to connect the
Transceiver(Terminals “A” & “B”) to the LonWorks network (See Figure 1). The
connection of the FTT-10 network is not polarity sensitive and the designation (+)
and (-) on the board is not relevant in this case. There are two sets of terminal “A” &
“B”. The second set of terminals can be used to extend the FTT-10 network (if
needed).
5.
Power up the MOD9200 Transceiver with the LON network.
6.
Use any LonWorks network management tool to setup the network, devices,
functional blocks, input and output variables (please refer to appendix A for nvo/nvi
names and SNVT types used).
7.
When setting up the MOD9200LON, the
Neuron ID
number is located on the label
inside of the device.