TABLE 3: 

VOLTAGE OUTPUT RANGE

Automation Components, Inc.

2305 Pleasant View Road  |  Middleton, WI 53562

Phone:

 1-888-967-5224  |  

Website:

 workaci.com

Page 4

Version: 9.0

I0000585

OUTPUT DIP SWITCH

1, 2, 4, 5 ON…………… all others off

1, 3, 4,6 ON……………..all others off

4, 5 ON………………..all others off

1,4, 7 ON.....................all others off

VOLTAGE OUTPUT 

 

0 – 5 V

1 – 5 V

0 - 10 V

2 – 10 V

TABLE 5: 

PRESET OUTPUT SPANS

OUTPUT DIP SWITCH

1,2,3,4 ON…………… 1, 2, 3, 4 ON

2,3,4 ON…………….. 1 OFF

1,3,4 ON……………… 2 OFF

1,2,4 ON..................... 3 OFF

3,4 ON……………...1,2 OFF

2,4 ON……………...1,3 OFF

1,4 ON……………...2,3 OFF

4 ON………………..1,2,3 OFF

1,2,3 ON…………...4 OFF

None ON…………..1,2,3,4 OFF

1,2,3 ON…………...4 OFF

VOLTAGE OUTPUT 

 

1V or 4mA 

3V or 12mA

4V or 16mA

5V or 20mA

6V

7V

8V

10V

Adj. 1 – 11V

Adj. 10 – 20V

Adj. 4 – 20mA

TABLE 4: 

CURRENT OUTPUT RANGE

OUTPUT DIP SWITCH

1, 2, 4, 5 ON…………… all others off

1, 3, 4,6 ON……………..all others off

VOLTAGE OUTPUT 

 

0 – 20 mA

4 - 20 mA

CALIBRATIONS OF INPUT SIGNAL OTHER THAN PRESETS SHOWN ON TABLE

1.) If you have an input range other than any presets shown above, set the input DIP switches to one of the 
three Adj. settings.  See inputs above in bold type.
2.) Apply the maximum of the input signal to terminals IN and COM.  With a volt meter measure the voltage 
from TP1 to the AIM2’s input side common (COM).  Turn the input Max. pot until the meter reads 5.00 ± 0.00 
V.  The maximum of the input signal is now calibrated.
3.) If the minimum of the input signal is zero, set input DIP switches 7 and 8 OFF and 6 ON.
4.) If the minimum of the input signal is other than zero, set maximum as in step 2, and use the following 
steps to set the minimum:

A.) Set switch 8 ON and 6 and 7 OFF.
B.) Produce the minimum signal value at the input terminal (IN).
C.) Measure the voltage between the TP1 test point and COM.  Record or remember.
D.) Now measure voltage between the TP3 test point and COM.  Adjust the input MIN pot until the 
voltage at TP3 is equal to the voltage recorded at TP1.  The minimum and maximum input signals are 
now calibrated.

SETTING AIM2 OUTPUT

FOR PRESET VOLTAGE OUTPUT RANGES:

  Make the following switch settings on output DIP switches.  

Set jumper J4 for E/Isnk (voltage/current sink), and J5 for SRC (source) output signal. See 

Table 3

.

FOR PRESET CURRENT OUTPUT RANGES:

  Make the following switch settings on output DIP switch.  If 

Source, set Jumper J4 to I and J5 to SRC.  If Sink, set J4 to E/Isnk, and J5 to SNK. See 

Table 4

.

FOR CALIBRATION OF AN ODD OUTPUT SIGNAL

Before proceeding, you must have already set up the 
input signal.  If not, return to page 3 and “SETTING 
AIM2 INPUT”.

Output ranges are selectable on the output DIP 
switch by setting offset (minimum signal) and spans 
available (maximum minus offset) are shown below.  
Find out if you can use a preset range by subtracting 
the minimum output signal (or offset) from the 
maximum.  For example, a 3.4 to 9.4 V signal output 
equals a 6 volt range, which is available as a preset, 
and the 3.4 volt offset can be adjusted.  Any span not 
listed below will have to be set from one of the 
adjustable range switch settings.

TO SET PRESET OUTPUT SPANS (Reference only 
switches 1 through 4, others are for OFFSET - See 

Table 5

).

Summary of Contents for AIM2

Page 1: ...le upon request for an additional charge This will speed up installation time for the end user MOUNTING INSTRUCTIONS Ground yourself to discharge static electricity before touching any electronic equipment as some components are static sensitive The interface device can be mounted in any position If circuit board slides out of snap track a non conductive stop may be required Use only fingers to re...

Page 2: ... Power 24 VAC Source Current or Voltage Output Signal Sink Loop Powered Current Input Connections using Internal VDC Supply Sink Current Output Two Wire Loop Powered Device Sink Loop Powered Current Output Connections using External VDC Supply Input Sink Current Connections 24VDC In Set Jumper For Sink Current Sink Loop Powered Current Output Connections using Internal VDC Supply Controller ...

Page 3: ...ING CONNECTIONS With the power OFF make the following connections Connect a 24 VAC power supply to the 24VAC terminals of the AIM2 Connect the input signal common to the COM input terminal of the AIM2 and the input signal positive to the IN input terminal of the AIM2 Connect the output signal common COM and the output signal positive OUT to their respective terminals on the controlled device SETTI...

Page 4: ...s other than zero set maximum as in step 2 and use the following steps to set the minimum A Set switch 8 ON and 6 and 7 OFF B Produce the minimum signal value at the input terminal IN C Measure the voltage between the TP1 test point and COM Record or remember D Now measure voltage between the TP3 test point and COM Adjust the input MIN pot until the voltage at TP3 is equal to the voltage recorded ...

Page 5: ...UT OFFSETS If your offset is not 0 1 or 2 volts you will need to adjust for your offset The offset can be adjusted from 0 to approximately 10V Adjustable 8 ON 5 6 7 OFF Generate the minimum input signal at the input terminals IN and COM and calibrate the output OFFSET pot until the offset required is reached check with a voltmeter at output terminals OUT and COM From this point on no further DIP s...

Page 6: ...0 mA 5 000Ω 500Ω 3 1 45 Captive screw Terminal Blocks 12 3 31 mm2 to 22 AWG 0 33 mm2 0 5 Nm Minimum 0 6 Nm Maximum 35 to 120 F 1 7 to 48 9 C 10 to 95 non condensing 20 to 150 F 28 9 to 65 5 C NON SPECIFIC INFORMATION Supply Voltage Supply Current Input Voltage Signal Preset Ranges Input Current Signal Preset Ranges Input Signal Adjustable Voltage Span Input Signal Adjustable Voltage Offset Input S...

Page 7: ...NOTES Page 7 Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Version 9 0 I0000585 ...

Page 8: ...nents Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Automation Components Inc 2305 Pleasant View Road Middleton WI 53562 Phone 1 888 967 5224 Website workaci com Version 9 0 I0000585 ...

Reviews: