Installation & Operation Manual
- Model VTS
Contents of this Manual are Subject to Change Without Notification
Page 15
6.4.1.1
Power Source Switch
The VTS Transmitter pcb has a Power Source Switch which should always be in the
“Operational Position” for the transmitter to function
normally
. The “Nonoperational
Position” is provided so the transmitter can be programmed or configured when there is no
24v power source available. This is a convenient feature for configuring the BACnet
parameters or
the transmitter’s analog output
prior to having the 24V power source wired.
Operational Position
Nonoperational Position
24V power is provided to the transmitter
through the 24V connector. This is the
normal position for the Power Source
Switch.
5Vdc power is provided to the
transmitter through the computer
connected to the USB Configuration Port.
This is a temporary position only.
Note:
The Power Source Switch must be returned to the Operational Position after
completing the configuration otherwise the transmitter will not function.
6.4.2
For connecting to the VTS through the Monitor (sold separately); remove the rubber
dust plug protecting the
Monitor’s U
SB port and insert the USB cable into the USB C
connector located on the Monitor. Be sure to reinstall the rubber dust plug on the
Monitor when finished.
1.
The Power Source Switch on the transmitter must be in the Operational Position
when the Monitor is connected. The Nonoperational Position shall not be used
when the Monitor is connected to the VTS.
2.
Verify the transmitter is powered prior to connecting the computer to the Monitor
USB port.
VTS
Factory cable provided
with Remote Monitor
Windows 10
Computer with
AccuStation
Insight Software
Remote Monitor
(sold separately)
Notes: