AccuTemp EDGE ALTLGB Owner'S Manual And Installation Instructions Download Page 8

Section I:  Installation

To check inlet pressure - with other equipment on 

the same line turned on and turned off:

Check the inlet pressure with all equipment on the same 

gas supply line turned on and turned off.
1. Shut off the gas supply and remove the cover panel of 

the control console.  Remove the inlet pressure tap and 

connect the pressure gauge or  manometer (See Fig. 1.4).
2. Turn the gas supply back on.  Light the main burner.  

Turning the primarythermostat dial above room 

temperature lights the main burner.
3. Record the inlet pressure readings on the Installation 

Checklist for Warranty Validation.  Be sure to take readings 

with other equipment on the same line turned on and 

turned off.
4. Reverse the procedure in step 2 to turn off the main 

burner and shut off the gas supply before disconnecting 

the manometer or pressure gauge.
5. Replace the inlet pressure tap plug.

Important! 

 Always shut off the gas supply at the manual 

valve in the gas supply piping to the unit (or at the tank 

for LP gas), before removing the inlet pressure tap plug to 

connect or disconnect a pressure gauge or manometer.  

Inlet Pressure Too High? 

 If natural gas pressure exceeds 

7” water column or LP gas pressure exceeds 14” water 

column, then a pressure-regulating valve must be 

installed in the gas supply line.  
I

nlet Pressure Too Low?

  If natural gas pressure is below 

5” water column or LP gas pressure is below 12” water 

column, then the installer must determine the problem.  

Too much equipment may be on the same line or a larger 

gas supply line may be required.

Inlet pressure must be correct before checking the outlet 

pressure.

Fig. 1.3  Pressure Regulator Specification Pressures

(in Inches Water Column)

Gas Valve 

Type

Type of 

Gas

Nominal Inlet 

Pressure Range

Factory Set 

Nominal Out-

let Pressure

Adjustment 

Setting Range

Intermittent 

Pilot

Natural

5.0 - 7.0” w.c.

3.5” w.c.

3 - 5

LP

12.0 - 14.0” w.c.

9.0” w.c.

8 - 12

Checking For Gas Leaks

WARNING:
Do not permanently supply gas to the unit until the gas 

lines have been pressure tested.  Faulty operation and 

even equipment damage will result if the gas supply falls 

below requirements.
The equipment and its individual shut-off valve must be 

disconnected from the gas supply piping system during 

any pressure testing of that system at test pressures in 

excess of 1/2 psi (3.5 kPA).
The equipment must be isolated from the gas supply 

piping system by closing its individual manual shut-off 

valve during any pressure testing of that system at test 

pressures equal to or less than 1/2 psi (3.5 kPA).

1.  Turn on the main gas supply.  With burner off, douse 

the pipe connections up stream of the ignition system 

control with a rich soap and water solution.  Bubbles 

indicate a gas leak.  If a leak is detected, tighten pipe 

connections.    Replace the part if the leak cannot be 

stopped.
2.  With main burner in operation, douse pipe joints 

and control inlet and outlet with rich soap and water 

solution.  If another leak is detected, tighten joints and 

pipe connections.  Replace the part if the leak cannot be 

stopped.

Gas Control - Pressure Verification

Using a pressure gauge or a manometer, the installer must 

record the gas pressure at both the inlet and outlet of the 

ignition system control—first with all equipment on the 

same gas line turned on, then with all equipment turned 

off.  These readings are necessary for your installation and 

warranty records.  Gas pressure input and output ratings 

for your equipment are listed on the unit’s nameplate.  

Acceptable pressure ranges are provided below.  Do not 

exceed these ratings.  NOTE:  Since outlet pressure is 

dependent upon proper inlet pressure, 

inlet pressure must 

be checked first.

6

Summary of Contents for EDGE ALTLGB

Page 1: ...THORIZED SERVICE AGENT EVACUATE ALL PERSONNEL FROM THE AREA WARNING IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE CAN CAUSE PROPERTY DAMAGE INJURY OR DEATH READ THE INSTALLATION O...

Page 2: ...bly 13 Actuator Maintenance Adjustment 14 Actuator Tension Adjustment 14 Actuator Repacking with Grease 14 Actuator Replacement 14 Fig 3 1 Actuator Components Assembly 15 Fig 3 2 Removing Installing A...

Page 3: ...for safe delivery to the customer until customer acceptance of the package Careful inspection of the packaging and the appliance should be completed before acceptance from the transportation company C...

Page 4: ...de cet appareil ou de tout autre appareil Always disconnect from the power supply and close the main gas valve before servicing The ignition system controls of this equipment have been factory set for...

Page 5: ...a power failure This appliance is equipped with a three prong grounding plug for your protection against shock hazard and should be plugged directly into a properly grounded three prong receptacle Do...

Page 6: ...restrict air movement into the equipment s combustion area or prevent proper combustion Adequate clearance for servicing and proper operation must be maintained Warning This unit is not suitable for...

Page 7: ...sed Connect the supply line to the ball valve at the rear of the unit Tighten the connection securely Electrical Connection A power cord is provided on the back of the unit for connecting to the elect...

Page 8: ...l Inlet Pressure Range Factory Set Nominal Out let Pressure Adjustment Setting Range Intermittent Pilot Natural 5 0 7 0 w c 3 5 w c 3 5 LP 12 0 14 0 w c 9 0 w c 8 12 Checking For Gas Leaks WARNING Do...

Page 9: ...main burner and shut off the gas supply before disconnecting the manometer or pressure gauge by reversing the procedure in Step 2 in the previous procedure for checking the inlet pressure 5 Replace th...

Page 10: ...tact with any electrical and control components For routine cleaning Accutemp s optional Care Kit accessories help you thoroughly clean all surfaces including the inside of the lid and the inside of t...

Page 11: ...mostat Dial Temperature Allows the user to set the cooking temperature of the unit Unit Power On Indicator Light Green Illuminates upon depressing the rocker switch to the ON position This indicates t...

Page 12: ...knob to the ON position and set the primary thermostat dial to the desired temperature setting How to Start Cooking 1 Press the rocker switch to ON position turn the primary thermostat clockwise to th...

Page 13: ...ut breaking the seal and returned to Accutemp The warranty is voided if the seal is broken or any attempt is made to recalibrate a thermostat See below for replacement instructions 1 Disconnect the un...

Page 14: ...ition System Control Disconnect power and turn off main gas supply before starting To replace the gas control valve Item 4 1 Disconnect the controls connector and the igniter connector from the gas co...

Page 15: ...r of burner assembly Item 9 Lift burner out of shroud Reverse steps to replace new burner D Replacing the Pilot Igniter Assembly Refer to steps in C Replacing the Gas Burner or Burner Orifices then Tu...

Page 16: ...ly later 5 Grasp the actuator sleeve and pull down away from the actuator rod The components inside the actuator sleeve will slide out 6 Pack the spring or springs with Bel Ray No Tox Clear Grease 2 T...

Page 17: ...COVER STOP 456695 1 8 Parts List TITLE PART NUMBER QTY ITEM SLEEVE WELDMENT 404483 001 1 1 ROD ACTUATOR LUG 455879 1 2 WASHER NYLON 1 355 X 52 408505 3 3 NYLON SHOULDER WASHER 408506 2 4 NUT SS LOCK 1...

Page 18: ...ilot gas control system The systems is as follows The SV9501 9502 SmartValve System Control combines gas flow control and electronic intermittent pilot sequencing functions into a single unit The Q345...

Page 19: ...sidual steam contained in the steam jacket Remove sight glass and place a funnel in the inlet elbow Pour water into funnel Continue adding water until the Fig 3 5 Examples of Problem Pilot Flames C Id...

Page 20: ...lain end that is not threaded is constructed of a material suitable for exposure to temperatures of 375 F or greater is of a pipe size equal to or greater than that of the valve outlet over its entire...

Page 21: ...er such as Klenzade XY 12 d Film remover such as Klenzade LC 30 Procedure 1 Clean food contact surfaces as soon as possible after use If the unit is in continuous use thoroughly clean and sanitize the...

Page 22: ...se off the sanitizer thoroughly 9 It is recommended that each piece of equipment be sanitized just before use 10 If there is difficulty removing mineral deposits or a film left behind by hard water or...

Page 23: ...stat setting too low Primary thermostat malfunc tioning Air in kettle jacket Uneven cooking due to cold spots Low gas pressure Plugged orifice s in burner Plugged burner supply tube Pilot Outages Low...

Page 24: ...on Pilot burner lights No Measure voltage to SV9500 Voltage must be at least 19 5 VAC No Check transformer line volt supply Yes Yes Main valve opens No Replace igniter sensor assembly and retain Rest...

Page 25: ...CP 1 8 npt 440280 Pigtail anti siphon SS 1 4 npt 456724 Safety relief valve 30 psi 425 lbs hr 3 4 npt Replaces part 440168 456727 Pressure gauge 30Hg 0 60 Replaces part 406732 406578 Terminal Block Ju...

Page 26: ...Section VI Parts List Actuator Parts List Assembly Fig 6 1 Actuator Assembly Diagram 24...

Page 27: ...2 3 1 Nut handle 408392 408392 408207 2 Handle round stainless steel 408359 408359 2 408360 3 Hex bonnet nut 450033 01 450032 01 440234 01 4 Faucet gland 460097 01 410228 01 440233 01 5 O ring 400382...

Page 28: ...ply with these codes Installation 1 Positioning the Unit 3 Verify the voltage requirements and electrical connections were checked Installation 3 Electrical Connection 4 Verify that a sediment trap an...

Page 29: ...the Continental United States and Hawaii They are available 7 days a week from 7 00 a m through 7 00 p m Eastern Standard Time Model No Purchased From Serial No Date Purchased Purchase Order No Locati...

Page 30: ...Wiring Diagram 120V 1PH 28...

Page 31: ...Wiring Diagram 240V 1PH 29...

Page 32: ...RELAY FOR 240 V RED LEAD TO RELAY FOR 208 V BLACK LEAD TO RELAY FOR 120 V TRANSFORMER 24 VOLT YELLOW 24 VAC BLUE 24 VAC BLACK BLACK ORANGE Honeywell 25V GND DIRECT SPARK IGNITION 25V BURNER VALVE VALV...

Page 33: ...rm the repair or replacement This warranty includes travel time not to exceed two hours and mileage not to exceed 50 miles 100 miles round trip but does not include post start up assistance or trainin...

Page 34: ...IMPORTANT SERVICE INFORMATION AccuTemp Product Inc Technical Customer Support Technician is available Monday thru Sunday 7 00am to 7 00pm EST...

Reviews: