8-2 External Sounders LC 1200 Manual
Mounting
Use a standard 2-1/2” deep single-gang box to
mount the
System Sensor
sounder with the two
mounting screws supplied at the desired
location.
Wiring
You will need 22-gauge, 2-conductor plenum-
rated cable for this connection.
To wire the
System Sensor sounder
to the LC
unit, refer to Figure 8.2 and use the following
instructions:
1. Using the RED wire, connect the
positive (+) terminal of the System
Sensor sounder to P2-5 (NC) of the LC
unit.
2. Using the BLACK wire, connect the
negative (-) terminal of the System
Sensor sounder to P3-4 (Ground) of the
LC unit.
3. Jumper P2-6 (Alarm Comm) to P3-3
(+12V DC) on the LC unit.
Figure 8.2 Wiring the
System Sensor
sounder
Multi-Tone Local Alert (MTLA)
Specifications
Mounting
Wiring
The Multi-Tone Local Alert (MTLA) (
Part #
300150; Figure 8.3;
System Sensor Chime CH1224
Series
), a wall-mount electronic chime, offers
multiple chime tones and is intended to attract
attention near the monitored zone.
The MTLA sound output is 54dBA at 12V DC
and 60dBA at 24V DC.
The chime has sixteen field-selectable tone
options, each with three volume settings. These
options are activated through the appropriate
settings on the DIP switch located on the rear of
the MTLA. Therefore, you can differentiate LC
units located in close proximity by using
separate tones.
Figure 8.3 The MTLA
Summary of Contents for LC 1200
Page 1: ...LC 1200 Manual 800 356 2671 Accutech www accutech ics com...
Page 2: ......
Page 8: ......
Page 10: ......
Page 12: ......
Page 20: ......
Page 21: ...LC 1200 Manual Chapter 2 The LC unit...
Page 22: ......
Page 33: ...LC 1200 Manual Chapter 3 Tags TAD Part s 77L016 67L016 660021...
Page 34: ......
Page 43: ...LC 1200 Manual Chapter 4 The Magnetic Switch Part 650514...
Page 44: ......
Page 49: ...LC 1200 Manual Chapter 5 Passive Infrared Reader PIR Part 300302...
Page 50: ......
Page 54: ...5 4 Passive Infrared Reader PIR LC 1200 Manual Figure 5 4 Wiring the PIR...
Page 56: ......
Page 57: ...LC 1200 Manual Chapter 6 The Keypad Part 650202...
Page 58: ......
Page 68: ......
Page 69: ...LC 1200 Manual Chapter 7 Push Button Override PBO Part 700022...
Page 70: ......
Page 74: ...7 4 Push Button Override PBO LC 1200 Manual Figure 7 2 Wiring the PBO to the LC unit...
Page 75: ...LC 1200 Manual Chapter 8 External Sounders Part s 700216 300150...
Page 76: ......
Page 80: ......
Page 81: ...LC 1200 Manual Chapter 9 Magnetic Locks Part s 700218 700228...
Page 82: ......
Page 86: ...9 4 Magnetic Locks LC 1200 Manual Figure 9 1 3101 Magnetic Lock PCB...
Page 87: ...LC 1200 Manual Magnetic Locks 9 5 Figure 9 2 Wiring the 3101 Magnetic Lock...
Page 91: ...LC 1200 Manual Magnetic Locks 9 9 Figure 9 4 Wiring a 3000 Series Magnetic Lock...
Page 92: ......
Page 93: ...LC 1200 Manual Chapter 10 Elevator Deactivation Part 700027...
Page 94: ......
Page 98: ...10 4 Elevator Deactivation LC 1200 Manual Figure 10 2 Wiring Elevator Deactivation...
Page 99: ...LC 1200 Manual Chapter 11 Automatic Door Deactivation Part 700033...
Page 100: ......
Page 103: ...LC 1200 Manual Chapter 12 Fire Panel Interface FPI Part 700013...
Page 104: ......
Page 106: ...12 2 Fire Panel Interface FPI LC 1200 Manual Figure 12 1 The FPI with cabinet...
Page 109: ...LC 1200 Manual Chapter 13 Timer Part 700018...
Page 110: ......
Page 114: ......
Page 115: ...LC 1200 Manual Chapter 14 Alert Panels Part s 700080 700050 700052...
Page 116: ......
Page 119: ...LC 1200 Manual Alert Panels 14 3 14 2 Wiring a SAP or GDP FPI also shown...
Page 121: ...LC 1200 Manual Chapter 15 System Maintenance Testing...
Page 122: ......
Page 130: ......
Page 131: ...LC 1200 Manual Chapter 16 FAQ Troubleshooting...
Page 132: ......
Page 136: ......
Page 137: ...LC 1200 Manual Appendix A Component Cut Sheets...
Page 138: ......