15-2 System Maintenance & Testing LC 1200 Manual
Zone, Lock Test
When a Tag approaches a monitored door zone
equipped with Locks, the Lock should engage.
When the Tag leaves the monitored zone, the
Lock should disengage. This test will evaluate
this operation.
Note:
In the event of a fire, all Locks are
disabled and the door can be opened
immediately.
Test results should be written down and kept in a
test log. Make your own, or use the included, to
ensure that every monitored zone is tested.
These test reports should become part of your
permanent quality assurance records.
1. Notify staff and security that you will be
testing zone performance and alarms
may
be generated. They should pay
special attention to traffic during this
time.
2. While not in a monitored zone, use a
TAD to activate the test Tag.
3. Hold the test Tag in your hand and
approach each monitored door zone.
4. Each door should lock as you approach.
NOTE:
You may be able to hear the lock
“click” as it changes states. Otherwise,
For 3000 Series Magnetic Locks, you
can push on the door to verify the Lock
is engaged. For 3101 Series Magnetic
Locks, the LED will turn from green to
red when the Lock is engaged.
However, do not open the door; this test
is intended only for verifying that a door
locks when a Tag approaches.
5. As you approach each zone, try varying
your approach angle (i.e., straight on,
from the sides, down low, etc.). Make
sure there is adequate coverage from all
angles leading to the monitored zone.
6. Record the results (pass or fail).
7. If the test fails to lock the door:
a. Notify staff and security of the
vulnerable area.
b. Check for visible damage or
tampering to the zone equipment.
c. Have a maintenance technician
verify power to the zone equipment.
d. Have a maintenance technician
verify the FPI is set properly.
e. Call your Accutech Representative.
8. To reset the Lock, deactivate the test
Tag or leave the monitored zone.
Depending upon your settings, the Lock
may disengage itself automatically.
Otherwise enter a Keypad Reset code.
Summary of Contents for LC 1200
Page 1: ...LC 1200 Manual 800 356 2671 Accutech www accutech ics com...
Page 2: ......
Page 8: ......
Page 10: ......
Page 12: ......
Page 20: ......
Page 21: ...LC 1200 Manual Chapter 2 The LC unit...
Page 22: ......
Page 33: ...LC 1200 Manual Chapter 3 Tags TAD Part s 77L016 67L016 660021...
Page 34: ......
Page 43: ...LC 1200 Manual Chapter 4 The Magnetic Switch Part 650514...
Page 44: ......
Page 49: ...LC 1200 Manual Chapter 5 Passive Infrared Reader PIR Part 300302...
Page 50: ......
Page 54: ...5 4 Passive Infrared Reader PIR LC 1200 Manual Figure 5 4 Wiring the PIR...
Page 56: ......
Page 57: ...LC 1200 Manual Chapter 6 The Keypad Part 650202...
Page 58: ......
Page 68: ......
Page 69: ...LC 1200 Manual Chapter 7 Push Button Override PBO Part 700022...
Page 70: ......
Page 74: ...7 4 Push Button Override PBO LC 1200 Manual Figure 7 2 Wiring the PBO to the LC unit...
Page 75: ...LC 1200 Manual Chapter 8 External Sounders Part s 700216 300150...
Page 76: ......
Page 80: ......
Page 81: ...LC 1200 Manual Chapter 9 Magnetic Locks Part s 700218 700228...
Page 82: ......
Page 86: ...9 4 Magnetic Locks LC 1200 Manual Figure 9 1 3101 Magnetic Lock PCB...
Page 87: ...LC 1200 Manual Magnetic Locks 9 5 Figure 9 2 Wiring the 3101 Magnetic Lock...
Page 91: ...LC 1200 Manual Magnetic Locks 9 9 Figure 9 4 Wiring a 3000 Series Magnetic Lock...
Page 92: ......
Page 93: ...LC 1200 Manual Chapter 10 Elevator Deactivation Part 700027...
Page 94: ......
Page 98: ...10 4 Elevator Deactivation LC 1200 Manual Figure 10 2 Wiring Elevator Deactivation...
Page 99: ...LC 1200 Manual Chapter 11 Automatic Door Deactivation Part 700033...
Page 100: ......
Page 103: ...LC 1200 Manual Chapter 12 Fire Panel Interface FPI Part 700013...
Page 104: ......
Page 106: ...12 2 Fire Panel Interface FPI LC 1200 Manual Figure 12 1 The FPI with cabinet...
Page 109: ...LC 1200 Manual Chapter 13 Timer Part 700018...
Page 110: ......
Page 114: ......
Page 115: ...LC 1200 Manual Chapter 14 Alert Panels Part s 700080 700050 700052...
Page 116: ......
Page 119: ...LC 1200 Manual Alert Panels 14 3 14 2 Wiring a SAP or GDP FPI also shown...
Page 121: ...LC 1200 Manual Chapter 15 System Maintenance Testing...
Page 122: ......
Page 130: ......
Page 131: ...LC 1200 Manual Chapter 16 FAQ Troubleshooting...
Page 132: ......
Page 136: ......
Page 137: ...LC 1200 Manual Appendix A Component Cut Sheets...
Page 138: ......