LC 1200 Manual Magnetic Locks 9-7
11. When you have completed the
adjustment, gently allow the door to be
pulled by the weight of the door.
NOTE:
When the door is closed the
LED will be Red, when the door is open
the LED will be Off.
12. Remove power from the Lock by
powering down the LC unit.
13. Tighten the set screw with the Allen
wrench provided. This will prevent the
Sensor pin from coming out of
adjustment.
NOTE:
Be careful not to over tighten.
14. Replace the Fire Alarm Control jumper
into the
N.C.
position (pins 1-2).
15. Move DS1 Position 1 into the
OFF
position.
NOTE:
This will take the lock out of
set-up mode and into normal operation
mode.
16. Move DS1 Position 3 into the
ON
position
17. Replace the cover to the Lock housing.
18. Apply power to the Lock from the LC
unit and test the function of the Lock.
Changing the Lock Nuisance delay time
The Lock Nuisance Delay time prevents
nuisance alarms by requiring a door disturbance
to be sustained for a set length of time before
registering an alarm.
The delay time is set by Position 3 on the
Selector Switch (S1) on the Lock PCB (
see
Figure 9.1
).
The OFF position results in a 1-second
delay
The ON position results in a 3-second
delay
Changing the Egress Alarm delay time
The Egress Alarm delay time requires a door
disturbance to be sustained for a set length of
time before unlocking the door and allowing
egress.
The delay time is set by Position 4 on the
Selector Switch (DS1) on the Lock PCB (
see
Figure 9.1
).
The OFF position results in a 15-
second delay
The ON position results in a 30-second
delay
Summary of Contents for 800121
Page 1: ...LC 1200 Manual 800 356 2671 Accutech www accutech ics com...
Page 2: ......
Page 8: ......
Page 10: ......
Page 12: ......
Page 20: ......
Page 21: ...LC 1200 Manual Chapter 2 The LC unit...
Page 22: ......
Page 33: ...LC 1200 Manual Chapter 3 Tags TAD Part s 77L016 67L016 660021...
Page 34: ......
Page 43: ...LC 1200 Manual Chapter 4 The Magnetic Switch Part 650514...
Page 44: ......
Page 49: ...LC 1200 Manual Chapter 5 Passive Infrared Reader PIR Part 300302...
Page 50: ......
Page 54: ...5 4 Passive Infrared Reader PIR LC 1200 Manual Figure 5 4 Wiring the PIR...
Page 56: ......
Page 57: ...LC 1200 Manual Chapter 6 The Keypad Part 650202...
Page 58: ......
Page 68: ......
Page 69: ...LC 1200 Manual Chapter 7 Push Button Override PBO Part 700022...
Page 70: ......
Page 74: ...7 4 Push Button Override PBO LC 1200 Manual Figure 7 2 Wiring the PBO to the LC unit...
Page 75: ...LC 1200 Manual Chapter 8 External Sounders Part s 700216 300150...
Page 76: ......
Page 80: ......
Page 81: ...LC 1200 Manual Chapter 9 Magnetic Locks Part s 700218 700228...
Page 82: ......
Page 86: ...9 4 Magnetic Locks LC 1200 Manual Figure 9 1 3101 Magnetic Lock PCB...
Page 87: ...LC 1200 Manual Magnetic Locks 9 5 Figure 9 2 Wiring the 3101 Magnetic Lock...
Page 91: ...LC 1200 Manual Magnetic Locks 9 9 Figure 9 4 Wiring a 3000 Series Magnetic Lock...
Page 92: ......
Page 93: ...LC 1200 Manual Chapter 10 Elevator Deactivation Part 700027...
Page 94: ......
Page 98: ...10 4 Elevator Deactivation LC 1200 Manual Figure 10 2 Wiring Elevator Deactivation...
Page 99: ...LC 1200 Manual Chapter 11 Automatic Door Deactivation Part 700033...
Page 100: ......
Page 103: ...LC 1200 Manual Chapter 12 Fire Panel Interface FPI Part 700013...
Page 104: ......
Page 106: ...12 2 Fire Panel Interface FPI LC 1200 Manual Figure 12 1 The FPI with cabinet...
Page 109: ...LC 1200 Manual Chapter 13 Timer Part 700018...
Page 110: ......
Page 114: ......
Page 115: ...LC 1200 Manual Chapter 14 Alert Panels Part s 700080 700050 700052...
Page 116: ......
Page 119: ...LC 1200 Manual Alert Panels 14 3 14 2 Wiring a SAP or GDP FPI also shown...
Page 121: ...LC 1200 Manual Chapter 15 System Maintenance Testing...
Page 122: ......
Page 130: ......
Page 131: ...LC 1200 Manual Chapter 16 FAQ Troubleshooting...
Page 132: ......
Page 136: ......
Page 137: ...LC 1200 Manual Appendix A Component Cut Sheets...
Page 138: ......