LC 1200 Manual System Maintenance & Testing 15-3
Zone, Egress Test
(3000 and 3101 Magnetic Locks)
Most monitored door zones equipped with
Locks are configured to generate an alarm if a
Tag is detected in the zone and the door is open.
This test will evaluate this operation.
NOTE:
In the event of a fire, all Locks are
disabled and the door can be opened
immediately.
This test should be conducted selectively; create
a rotating schedule to test a different set of zones
each time that periodic testing is conducted.
Test results should be written down and kept in a
test log. Make your own, or use the included, to
ensure that every monitored zone is tested.
These test reports should become part of your
permanent quality assurance records.
1. Notify staff and security that you will be
testing zone performance and alarms
will
be generated. They should pay
special attention to traffic during this
time.
2. Prop the door open.
3. While not in the zone, use a TAD to
activate the test Tag.
4. Approach the door. An alarm should
sound.
5. Record the results (pass or fail).
6. If the test fails to cause an alarm:
a. Notify staff and security of the
vulnerable area.
b. Check for visible damage or
tampering to the zone equipment.
c. Have a maintenance technician
verify power to the zone equipment
d. Have a maintenance technician
verify the FPI is set properly
e. Call your Accutech Representative.
7. To reset the zone, enter a Keypad reset,
deactivate the test Tag, and close the
door completely, and if necessary, clear
the alarm on the PC.
Zone, Delayed Egress Test
(3101 Magnetic Locks only)
Delayed Egress Circuitry is a feature of the
Accutech 3101 Magnetic Lock that, due to fire
and life safety codes, allows free egress through
a door after 15 seconds (plus a 1 to 3 second
nuisance delay) of constant force is applied. This
test will evaluate this operation.
NOTE:
In the event of a fire, Delayed Egress
Circuitry is disabled and the door can be opened
immediately.
This test should be conducted selectively; create
a rotating schedule to test a different set of zones
each time that periodic testing is conducted.
Test results should be written down and kept in a
test log. Make your own, or use the included, to
ensure that every monitored zone is tested.
These test reports should become part of your
permanent quality assurance records.
Summary of Contents for 800121
Page 1: ...LC 1200 Manual 800 356 2671 Accutech www accutech ics com...
Page 2: ......
Page 8: ......
Page 10: ......
Page 12: ......
Page 20: ......
Page 21: ...LC 1200 Manual Chapter 2 The LC unit...
Page 22: ......
Page 33: ...LC 1200 Manual Chapter 3 Tags TAD Part s 77L016 67L016 660021...
Page 34: ......
Page 43: ...LC 1200 Manual Chapter 4 The Magnetic Switch Part 650514...
Page 44: ......
Page 49: ...LC 1200 Manual Chapter 5 Passive Infrared Reader PIR Part 300302...
Page 50: ......
Page 54: ...5 4 Passive Infrared Reader PIR LC 1200 Manual Figure 5 4 Wiring the PIR...
Page 56: ......
Page 57: ...LC 1200 Manual Chapter 6 The Keypad Part 650202...
Page 58: ......
Page 68: ......
Page 69: ...LC 1200 Manual Chapter 7 Push Button Override PBO Part 700022...
Page 70: ......
Page 74: ...7 4 Push Button Override PBO LC 1200 Manual Figure 7 2 Wiring the PBO to the LC unit...
Page 75: ...LC 1200 Manual Chapter 8 External Sounders Part s 700216 300150...
Page 76: ......
Page 80: ......
Page 81: ...LC 1200 Manual Chapter 9 Magnetic Locks Part s 700218 700228...
Page 82: ......
Page 86: ...9 4 Magnetic Locks LC 1200 Manual Figure 9 1 3101 Magnetic Lock PCB...
Page 87: ...LC 1200 Manual Magnetic Locks 9 5 Figure 9 2 Wiring the 3101 Magnetic Lock...
Page 91: ...LC 1200 Manual Magnetic Locks 9 9 Figure 9 4 Wiring a 3000 Series Magnetic Lock...
Page 92: ......
Page 93: ...LC 1200 Manual Chapter 10 Elevator Deactivation Part 700027...
Page 94: ......
Page 98: ...10 4 Elevator Deactivation LC 1200 Manual Figure 10 2 Wiring Elevator Deactivation...
Page 99: ...LC 1200 Manual Chapter 11 Automatic Door Deactivation Part 700033...
Page 100: ......
Page 103: ...LC 1200 Manual Chapter 12 Fire Panel Interface FPI Part 700013...
Page 104: ......
Page 106: ...12 2 Fire Panel Interface FPI LC 1200 Manual Figure 12 1 The FPI with cabinet...
Page 109: ...LC 1200 Manual Chapter 13 Timer Part 700018...
Page 110: ......
Page 114: ......
Page 115: ...LC 1200 Manual Chapter 14 Alert Panels Part s 700080 700050 700052...
Page 116: ......
Page 119: ...LC 1200 Manual Alert Panels 14 3 14 2 Wiring a SAP or GDP FPI also shown...
Page 121: ...LC 1200 Manual Chapter 15 System Maintenance Testing...
Page 122: ......
Page 130: ......
Page 131: ...LC 1200 Manual Chapter 16 FAQ Troubleshooting...
Page 132: ......
Page 136: ......
Page 137: ...LC 1200 Manual Appendix A Component Cut Sheets...
Page 138: ......