0
IO Modual
When DO circuits work in energy output mode, parameters of DO energy
pulse constant should also be set correctly, which include “active pulse
constant (100aH)” and “reactive pulse constant (100bH)”, as shown in
figure 3-8.
The value of pulse constant should satisfy following expression:
Pulse constant >( +1) ×
In the expression, the “Pmax” is the maximum power or reactive power.
The unit is watt or var. Recommend pulse constant is 3 to 5 times the
right side value of the above expression
.
3.5 Analog Output
1. Analog Output Relationship with Electrical Quantities
The analog output circuit can convert anyone of 30 electrical quantities
(reference to Acuvim II User’s Manual), which is selected by user, to
analog voltage or current.
The analog output circuit supplies 4 output modes, including 0 to 20mA
mode, 4 to 20mA mode, 0 to 5V mode and 1 to 5V mode.
Figure 3-9 shows the relationship between analog output and various
electrical quantities.
45
65
0
20
mA
Frequency(Hz)
400
mA
Phase Voltage(V)
Line Voltage(V)
Current(A)
Phase Active/Reactive
Power(W/Var)
Total Active/Reactive
Power(W/Var)
mA
Phase Apparent
Power(VA)
Total Apparent
Power(VA)
0
20
mA
Power Factor
0.5C
10
1
0.5L
0-20mA output mode
69
24
480
0
0
20
24
690
mA
828
0
0
20
24
5
mA
6
0
0
20
24
2000
mA
2800
0
-2000
20
24
6000
mA
8400
0
-6000
20
24
20002400
0
0
20
24
6000
mA
7200
0
0
20
24
DO Pulse Width
20
Pmax
18×10
6
Summary of Contents for Acuvim II AXM-IO1
Page 1: ...MetersUSA www MetersUSA com Meters MetersUSA com Ph 1847 302 7691 Fx 1847 375 9523...
Page 2: ......
Page 11: ...6 Chapter 2 Installation Appearance and Dimesions Installation Method Wiring of IO Modules 5...
Page 22: ...16 IO Modual...
Page 41: ...IO Modual 35 Figure 3 13 Parameter setting of IO modules...
Page 42: ...36 IO Modual...
Page 46: ...40 IO Modual Appendix B Ordering Information Type AXM IO1 AXM IO2 AXM IO3...
Page 47: ...IO Modual 41 Appendix C Revision History Revision Date Description 1 0 20070915...
Page 48: ...42 IO Modual...
Page 49: ......
Page 50: ......