IO Modual
5
Figure 3-6 recorded number of pulses read by the utility software
Parameter Setting of Counting of Input Pulses:
Take AXM-IO11 (AXM-IO1 module in sub address 0) for example.
1. “109eH” register: if the bit is set as “1”, the counterpart digital input
circuit is set to be a counter of input pulses.
2. “109fH” register: this register is an unsigned integer. If this register is
A , and the digital input circuit is set to be a counter of pulses, then the
real number of pulses counted by this DI circuit will as follow:
real number of pulses = A × recorded number of pulses.