IO Modual
4 digital inputs (DI), each digital input can be used to detect remote
signals, or be used as a counter of input pulses. When it is used to detect
remote signals, it also can enable SOE(sequence of events), recording the
events and time of the events.
2 analog outputs (AO), it can output analog voltage or analog current.
When it outputs analog voltage, the range of voltage is from 0 to 5V or
from 1 to 5V. When it outputs analog current, the range of current is
from 0 to 20mA or from 4 to 20mA.
2 digital outputs (DO), it can work in alarm mode, or work in energy pulse
output mode. Both of 2 digital outputs work in the same mode. When it
works in energy pulse output mode, it can output various types of energy.
AXM-IO3 module,
which is adapted to electrical devices, is composed of:
4 digital inputs (DI), each digital input can be used to detect remote
signals, or be used as a counter of input pulses. When it is used to detect
remote signals, it also can enable SOE(sequence of events), recording the
events and time of the events.
2 relay outputs (RO), it can work in controlling mode, or work in alarm
mode. Both of 2 relay outputs work in the same mode. When it works
in controlling mode, it has two optional output modes, latching mode
and pulse mode. When it works in alarm mode, it has only one latching
output mode.
2 analog inputs (AI), it can detect input analog voltage or analog current.
When it detects input analog voltage, the range of voltage is from 0 to
5V or from 1 to 5V. When it detects input analog current, the range of
current is from 0 to 20mA or from 4 to 20mA.
Summary of Contents for Acuvim II AXM-IO1
Page 1: ...MetersUSA www MetersUSA com Meters MetersUSA com Ph 1847 302 7691 Fx 1847 375 9523...
Page 2: ......
Page 11: ...6 Chapter 2 Installation Appearance and Dimesions Installation Method Wiring of IO Modules 5...
Page 22: ...16 IO Modual...
Page 41: ...IO Modual 35 Figure 3 13 Parameter setting of IO modules...
Page 42: ...36 IO Modual...
Page 46: ...40 IO Modual Appendix B Ordering Information Type AXM IO1 AXM IO2 AXM IO3...
Page 47: ...IO Modual 41 Appendix C Revision History Revision Date Description 1 0 20070915...
Page 48: ...42 IO Modual...
Page 49: ......
Page 50: ......