Chapter 3: Operation & Application
33
To input the user password, users will use the “SCROLL” key to change the value of the flashing
digit. The “SET” key is used to move between digits and to confirm the entered password when
on the last digit.
After entering the correct password, the AcuRev 1310 will direct users to the device address con-
figuration of the meter.
Note: Users will be redirected back to the important parameters screen after entering the pass-
word if the physical/electronic seal is enabled.
In the setting mode there will be an “S” in the top row followed by the setting page number.
After a minute of inactivity in this mode, the meter will be redirected back to the important pa-
rameter display. If the “SCROLL” key is pressed and held, the meter will also be redirected out
of the settings mode.
Note:
The default password of the meter is 0000.
Note:
The ‘SET’ key is located under the meters terminal cover.
In the settings mode, the following operations apply for the keys:
The “SET” key is used to enter edit mode of the setting and to confirm the setting change.
The “SCROLL” key is used to move to the next setting page and to change the value of the set-
ting when in edit mode.
The following tables will show the Setting Display for the different AcuRev 1310 Series Meters.
Table 3-6 Setting Display for
AcuRev 1311
Page
Parameter
Range
1
Device Address
1-247
2
Password
0000-9999
3
Real Time Metering Mode
1: Primary 2: Secondary
4
Voltage Wiring
3LN; 1LL; 1LN; 2LL
5
CT2
5A/1A(5A Current Input)
80mA/100mA/200mA(mA Current Input)
333mV
RCT
6
CT1
1~50,000
7
PT2
50~400
8
PT1
50~1000000
9
Pulse Constant
1~60000
10
Pulse Width
20~100ms
11
Energy Decimal Places
0-3
12
Custom Data Display: Add