Table 4.9 depicts the response of V=402851D8H(2.6299953V).
Addr
Fun
Byte count
Data1
hi
Data1
lo
Data2
hi
Data2
lo
CRC16 hi
CRC16 lo
01H
03H
04H
40H
28
51
D8
52
31H
Table 4-9 Response frame of reading voltage
4. Control Relay Output (Function Code 05)
Query
This query frame forces the relay status to ON or OFF. AcuDC 240 relay output address
starts from 0000H(Relay1=0000H,Relay2=0001H).
Data FF00H changes the relay status to ON, data 0000H changes the relay status to OFF.
The relay will not be influenced by any other data input
The following is to query slave device 1 to set relay status as ON.
Addr Fun
Do addr hi
Do addr lo
Value hi
Value lo
CRC16 hi
CRC16 lo
01H
05H
00H
00H
FFH
00H
8CH
3AH
Table 4-10 Control relay status query frame
Response
The correct response to this request is to send back the received data after the relay status
is changed.
Addr Fun
Do addr hi
Do addr lo
Value hi
Value lo
CRC16 hi
CRC16 lo
01H
05H
00H
00H
FFH
00H
8CH
3AH
Table 4-11 Control relay status response frame