17
output, please specify when ordering.
Analog Output can be used for scaling current, voltage, power. The output type is fixed
(0-20mA/4-20mA or 0-5V/1-5V), the output range can be configured.
AcuDC 240 series can be configured via pressing the buttons on the meter. The meter with
communication option can be configured via our software.
1. Select AO parameter.
2. Set AO upper and lower limits. For voltage, it can be set as 0% - +100%. For current and
power, it can be set as 0% - +100%, 0% - -100%,-100% - +100% and 0 - ±100%. Selecting
the proper upper and lower limits improves AO accuracy and efficiency.
3. The relationship between AO and its related parameter:
Figure 2-14 Analog Output
VCC
R2
Vout
AcuDC 240
R1
AO+
AO-
AO-
AO+
VCC
R1
Vout
AcuDC 240
Load
Load
Current Output
Voltage Output