26
AcuDC 210/220 Series
Analog Output
One analog output (AO) channel can be added to the AcuDC 210/220 meter as an
option. Two types of AO signals are available: 4-20mA or 0~5V. Each meter can only
support one type of output (either 4~20mA option or 0~5V option). Please specify
your analog output requirement before ordering.
Analog output can track voltage, current and power. The output range is
fixed(4~20mA or 0~5V),but the input range can be set for different applications.
Setting procedure is as follows:
Analog output settings can be modified by pressing the front panel keys on all
AcuDC 210/220 Series models. In addition to front panel key pressing, AcuDC 220
Series' setting can be modified using RS485 communication.
1. Select track object: voltage, current or power.
2. Set tracking for the upper and lower limit. Maximum upper limit values for
voltage, current and power are 600V, 9999A, 6000kW respectively. The upper limit
must be less than the maximum upper limit value and greater than the lower limit