SPECIFICATIONS  –  GX  MODEL

Applications:

Use  for  indoor  or  outdoor  applications  where  occasional 

moisture is common.

Materials:

Acetal, Amorphous Nylon, Silicone Rubber, Polyester (de-

cals),  Viton  (gasket  &  seals),  Stainless  Steel  (fasteners).

Power Source:

2-wire, loop powered. 8.5 VDC to 35 VDC loop voltage re-

quired for correct operation.

Outputs

*

:

Analog Primary:  4-20 mA current loop. With loop voltage 

maintained within specified limits, will maintain advertised

linearity over 4 mA to 20 mA range, with good linearity in 

over-range conditions to about 1.5 mA and 25 mA.
Analog Auxiliary:  0 to 5 VDC. Relationship to primary current 

output: V (volts) = l (ma) ÷ 5 . Will maintain advertised linearity 

over 0.8 V to 4.0 V range, with good linearity in over-range 

conditions to about 0.1 V and 4.9 V.

Recommended minimum driven impedance = 10K Ohms.
Digital (Pulse-Out):  Open Collector, square wave. Will switch 

up to 60 V and up to 200 mA. Closed circuit voltage drop 

typically 0.1 V; guaranteed less than 0.5 V at any current up 

to 200 mA.

Configuration:

2-Totals (1 cumulative and 1 batch), Rate, 2 Cals (Factory 

calibration, field calibration).

Time Base:

Minutes

Unit of Measure:

U.S. gallons, litres or cubic feet.

Accuracy/Performance:

Possible conversion error, in addition to any inaccuracy of 

coupled flowmeter, as follows:
Max. Conversion Error:  (Nonlinearity plus span, any input, 

loop  current  output,  0°  C  to  +70°  C,  loop  voltage  supply 

12 VDC to 24 VDC) 0.5% of span plus possible resolution 

uncertainty.
Max.  Conversion  Resolution  Uncertainty:    (Loop  current 

output,  when  properly  calibrated)  Larger  of  0.1  mA  or 

[20  mA  /  (10  x  (  f

20

–f

4

)].  Where  f

20

  =  frequency  at  20  mA,

f

= frequency at 4 mA.

Speed of Response:  After step change in input frequency, 

loop output guaranteed stable within 3 x accumulating time 

(Accumulating time user selectable from 0.3 sec, 0.7 sec, 

1.3 sec, 2.6 sec, 5.2 sec).

Frequency Range:

0.25 to 1,000 hertz

Batch Total:

Up to 999,999 x 100 (99,999,999)

Cumulative Total:

Up to 999,999 x 100 (99,999,999)

Temperature:

  Ambient Temperature:  +32° F to +140° F (0° C to +60° C)

Cable:

20 ft., 3 conductor, shielded (Belden 9363).

Mechanical Connections:

Display is mounted directly to flow meter body via 1-inch NPT.

Electrical Connections:

One strain relief port: one threaded plug (1/2 x 20).

Weight:

1.1 lb. (.5 kg) (Additional)

*

  If you want to use the 4-20 mA output and one or both of the other outputs 

at the same time, you must provide electrical isolation between the current loop 

and all other circuit elements. Failure to do so will result in incorrect 4-20 mA 

signal conversion, and possible damage to the unit.

Summary of Contents for TM Series

Page 1: ...the nozzle Installation to metal connections is not recommended Install as follows 1 Plan to install turbine with a minimum straight pipe length as follows Upstream from the turbine allow a minimum st...

Page 2: ...Type Turbine Wetted Components Housing PVC Journal Bearings PEEK Shaft Stainless Steel Rotor and Nose Cone Acetal Washers Stainless Steel Max Working Pressure TM300 All Models 225 PSIG 73 F TM400 All...

Page 3: ...n hazardous locations Be sure O rings and seals are kept in good repair When applying power use DC power only Disconnect external power before attaching or detaching input or output wires Installation...

Page 4: ...Switching between different units will not corrupt the Total s contents For example in GL mode the computer totalizes 10 00 gallons if the user switches to LT mode the display will read 37 85 litres...

Page 5: ...minemaximumpowersupplyvoltageafterdetermin ing maximum allowable voltage of all electronic devices in the system 5 WIRING CAUTION T E R M I N A L L O C A T I O N S 9V_BAT Battery 6 5V to 20V EXT_V Ext...

Page 6: ...wer OUTPUT P U R S I G N A L O U T P U T Connect signal wire to OC_OUT terminal Connect ground wire to any COM terminal NOTE Jumper should not connect pins marked Output P U R Open Collector OUTPUT P...

Page 7: ...006 44 To replace the battery 1 Remove the two large screws and two small screws from the battery coverplate 2 Remove the battery coverplate and gasket 3 Remove the battery and clean any corrosion fro...

Page 8: ...100 ft 1 12 902005 9 Strain Relief 1 13 901002 87 O Ring 1 Item No No Part No Description Req d 14 906005 47 Threaded Plug 1 15 906005 48 Seal 1 16 904005 63 Screw 4 40 x 3 16 in 2 17 42100117 Jumper...

Page 9: ...powered and provides a 4 20 mA analog output propor tional to the frequency signal for communication with PLCs and other customer equipment The 4 20 mA or 0 20 mA output is calibrated under actual flo...

Page 10: ...ction to cor rectly wire the system The display is externally powered by the loop Determine maximum power supply voltage after determin ing maximum allowable voltage of all electronic devices in the s...

Page 11: ...Max V 35 Customer Equipment NOTE Minimum loop power supply voltage required 8 5V Max Customer Equipment Drop Wiring IR Drop CAUTION When reassembling the faceplate make sure that the enclosure seal is...

Page 12: ...Power Supply Typ 12 24 VDC 0 5 V Analog Input Analog In Return 0 5 V Output Local Com TM Meter NOTE 1 Loop power supply electrically isolated from customer equipment NOTE 2 Actual value of loop curre...

Page 13: ...upt the Total s contents For example in GL mode the computer totalizes 10 00 gallons if the user switches to LT mode the display will read 37 85 litres the same volume different unit OPERATION The fie...

Page 14: ...ght press and hold both its SET and 20 buttons Release them when the light blinks NOTE During the high and low setpoint procedure if the new settings are very different from the previous settings it i...

Page 15: ...itu ations where sensor output frequency fluctuates or wobbles substantially The GPI 4 20 mA Out with Display offers a choice of five response time settings selectable by the unit s pushbuttons Proced...

Page 16: ...signal input connections for intermittent open or short circuits F LOOP OUTPUT 1 Output response time setting too long Select a shorter response time setting STABLE BUT especially for fast input sign...

Page 17: ...20 ft 1 125066 3 Cable 100 ft 1 Item No No Part No Description Req d 13 906005 47 Threaded Plug 1 14 902005 9 Strain Relief 1 15 901002 87 O Ring 1 17 120054 01 Main Circuit Assembly 1 18 904005 28 S...

Page 18: ...feet Accuracy Performance Possible conversion error in addition to any inaccuracy of coupled flowmeter as follows Max Conversion Error Nonlinearity plus span any input loop current output 0 C to 70 C...

Page 19: ...CE All information needed for the GA Model can be found in the GX Model sections Consult one or all of the following Important Notice 9 Safety Instructions 9 Installation 9 Wiring 10 Wiring Diagrams 1...

Page 20: ...ironmental Avoid plumbing meter where the Scaled Pulse Module is Subject to constant exposure to water or other liquids oc casional low pressure splashing will not harm unit if cable entry points are...

Page 21: ...mA and a maximum open circuit voltage of 60 V Be sure that you never exceed these limits NOTE Do not apply any AC voltage to this output as the internal device may be damaged The output produces a si...

Page 22: ...de screwdriver or similar tool simply set the module s K factor switches to this number WARNING OPERATION K F A C T O R S W I T C H E S X X X X X The X markers represent the digits of the K factor Thi...

Page 23: ...d an output pulse for every whole unit please contact the factory It is possible to supply on special order units with a K factor range of 00000 to 9999 9 i e no decimal place Check cable entry seals...

Page 24: ...t factory C EXTRA OR ERRATIC 1 Signal picking up electronic Use shielded or shorter sensor cable OUTPUT PULSES WHEN noise USING ANY INPUT 2 Electronic failure Contact factory D EXTRA OR ERRATIC 1 Usin...

Page 25: ...Coverplate Kit 1 2 12052101 Circuit Assembly Kit 1 3 120517 01 Adapter Kit 1 4 125066 20 Cable 20 ft 1 5 901002 82 O Ring 1 6 901002 87 Seal 2 7 902005 9 Strain Relief 2 8 904002 44 Sealing Screw 1 4...

Page 26: ...ion in 2003 This symbol indicates that this product contains electrical and electronic equipment that may include batteries printed circuit boards liquid crystal displays or other components that may...

Page 27: ......

Page 28: ...fied outside the warrantor s duly appointed representative B the product has been subjected to neglect misuse abuse or damage or has been installed or operated other than in accordance with the manufa...

Reviews: