11
CAUTION: When reassembling the faceplate,
make sure that the enclosure seal is not
crimped or twisted. Do not over-tighten
corner screws (hand tighten only). Face-
plate can be rotated 90°.
W I R I N G D I A G R A M 1
— 4-20 mA or 0-20 mA Output —
Customer Equipment With Built-in Power Supply
Output: Customer Equipment, 0-20 mA Sensing, Built-in Loop Power Supply
TM Meter
INPUTS
OUTPUTS
4-20 mA Out
with Display
Loop (+)
Loop (–)
(current)
(current)
Min. V = 8.5
Max. V = 35
Customer
Equipment
NOTE: Minimum loop power supply voltage required:
8.5V + (Max - Customer - Equipment - Drop) +
(Wiring - IR - Drop)
CAUTION: When reassembling the faceplate,
make sure that the enclosure seal is not
crimped or twisted. Do not over-tighten
corner screws (hand tighten only).
Faceplate can be rotated 90°.
W I R I N G D I A G R A M 2
— 4-20 mA or 0-20 mA Output —
Customer Equipment Without Built-in Power Supply
Output: Customer Equipment, 0-20 mA Sensing, Separate Power Supply
TM Meter
INPUTS
OUTPUTS
4-20 mA Out
with Display
Loop (+)
Loop (–)
(current)
(current)
Min. V = 8.5
Max. V = 35
Customer Equipment
(+)
(–)
Loop Power Supply
Typ 12 – 24 VDC
Loop (+) Input
Loop (–) Input
Summary of Contents for TM Series