Easy service access is provided by unbolting manhole lid through which pump is
mounted and removing entire assembly. Use proper thread sealant and insert gas-
ket between flanges of floating suction and pump. This prevents hindrance to pump
performance when product level is below this point.
Red Jacket pumps are centrifugal type pumps and as such
are not designed to pump product when the level is below the
bottom end of the UMP.
14" APPROX.
4" APPROX.
OPENING FOR GAUGING AND
ADJUSTING CABLE
MANHOLE:
SHOULD BE LARGER THAN MANHOLE
WELDED ON TANK. KEEP AREA OPEN
DOWN TO TANK.
NOTICE
NOTICE
Figure 1.2 Floating suction installation
R
ECOMMENDED
F
LOATING
S
UCTION
I
NSTALLATION
Distance between center line of pump motor and center line
of bottom fill tube should be 3’ minimum. Air locking of pump
after product delivery may occur at distances less than this.
We supply adapter only; not the apparatus. Floating suction
adapter is not available for the X5 Model pump.
•
The floating suction arm can be mounted to pump previous to installing in tank.
See example of adaptation to floating suction assembly below.
Figure 1.3 Floating Suction Adapter
2" N.P.T.
FEMALE
THREAD
14"
BOTTOM OF THE TANK
NOTICE
— 3 —
Summary of Contents for Red Jacket AGUMP33R1
Page 14: ...8 4 Petroleum AG...