TECHNICAL CHARACTERISTICS

 

The 

HPE

 water chillers and heat pumps series are designed for residential and industrial applications, these units are extremely 

versatile and can operate in heat pump mode with the ability of hot water production at a temperature up to 65°C for 

environmental heating and sanitary applications with the utilization of electric heaters. 

The use of brushless inverter compressor technology, matched with the electronic expansion valve and to the pump and the 

variable speed blower are generally used for optimizing the power consumption and the operative efficiency of the refrigerating 

components of the whole system. 

5.1

 

FRAME 

All i-HP units are made up of hot-galvanised thick sheet metal, painted with polyurethane powder enamels at 180°C to ensure the 

best resistance against atmospheric agents. The front panel is hinged to the lift side to allow access to the internal components for 

inspection and maintenance. The screws and the inserts are made up of galvanized steel. 

5.2

 

REFRIGERANT CIRCUIT 

The refrigerant circuit has been manufactured according to the UNI EN 13134 directive concerning welding procedures. The 

refrigerant gas employed in these units is R410A type. The refrigerant circuit includes in its basic version: 4-way reversing cycle 

valve, electronic expansion valve, liquid separator, liquid receiver, check and maintenance valves, pressure safety device according 

to PED regulation (high pressure switch), and pressure transducers to accurately adjust the evaporating and condensing pressures, 

filters for expansion  valve to prevent its clogging. The versions with vapour  injection also include heat exchanger to produce 

vapour, electronic injector valve, and the ON-OFF valves of injection in case of two compressors. 

5.3

 

COMPRESSORS 

The compressors are scroll type DC inverter designed for use with R410A refrigerant, and are mounted on a rubber material acting 

as a shock absorber. The compressors of the injection versions are designed to optimize the efficiency of the refrigerant cycle 

under low ambient temperatures conditions and are supplied with connection for vapour injection. 

The crankcase heater operates when the compressor remains off for at least 30 minutes and if the discharge temperature is below 

20°C (with hysteresis of 2.0°C). When the compressor restarts, the crankcase heater will stop operation. We recommend to turn 

on the unit and to put it in standby mode at least 6 hours before the first start-up. 

The checking of the compressors is possible through the front panel of the unit that allows the maintenance of the compressors 

even if the unit is in operation. 

5.4

 

AIR-SIDE EXCHANGER 

The air-side heat exchanger is made up of copper pipes and aluminium fins. The copper pipes diameter is 7,94 mm, the thickness 

of the aluminium fins is 0,12 mm. The pipes are mechanically expanded into the aluminium fins in order to improve the heat 

transfer coefficient. The geometry of this heat exchanger ensures a low value air-side pressure drop and then it allows the use of 

fans with low number of revolutions (with the advantage of reducing the unit noise level). 

5.5

 

FAN MOTOR 

The fan motor is axial type with plastic aerofoil blades. It is statically and dynamically balanced and supplied with a safety fan 

guard. The fan motor is a modulated brushless type, directly coupled and equipped with an integrated thermal overload 

protection. The protection class of the motor is IPX4 according to CEI EN 60529. 

5.6

 

USER-SIDE HEAT EXCHANGER 

The user-side heat exchanger is made up of AISI 304 stainless steel braze-welded plates type, and is factory insulated with flexible 

close cell material and is equipped with an antifreeze electric heater (optional accessory: KA). Each evaporator is equipped with a 

temperature sensor for antifreeze protection that activates the circulator, even in the case where the unit is turned off when 

meeting the setting parameters by controller. 

5.7

 

ELECTRICAL CONTROL PANEL 

The electrical control panel board is manufactured according to European Union directives currently in force. To access to the 

electrical control panel board, put the disconnect switch in the Off position, (presence of a door lock system) and wait until fan 

blades have come to a complete stop, open the front panel by removing the three screws with a flat-head screwdriver, turn to 

open quarter-turn the two locks of the electric control panel board. The protection degree is IP34. The electric box is supplied with 

a terminal block completed with free contacts for remote ON-OFF,  and for winter/summer change over. The addition of the 

optional module GI enables the management of further functions of the plant. 

5.8

 

CONTROL SYSTEM 

The 

HPE

  units are equipped with a microprocessor adopting an overheating control logic program through the electronic 

thermostatic valve managed by the pressure transducers signals and temperature sensor. The CPU also manages the following 

functions: water temperature regulation, antifreeze protection, compressors’ time setting, alarm reset, alarms management and 

operation LED. Upon request, the microprocessor can be connected to a BMS remote control system and to the simpler HNS 

system with our terminal units. The control system together with the INVERTER technology and the on board sensors can 

continuously monitor and adapt the performance of the inverter compressor, of the circulator pump and of the fan motor. 

5.9

 

CONTROL AND PROTECTION DEVICES 

The units are standard equipped with the following control and protection devices: return water temperature sensor installed on 

the return water pipe line from the plant, operating and antifreeze sensor installed on the outlet water pipe to the plant, high 

Summary of Contents for HPE 35

Page 1: ...TECHNICAL INFORMATION HPE 25 70 HPE LT 25 50 INVERTER Air water inverter heat pumps with axial fans and steam injection versions HPE 25 70 HPE LT 25 50 INVERTER...

Page 2: ...m the application of Directive 2014 68 UE Reference to Art I paragraph 2 point f L attrezzatura a pressione rientra nella CAT I L unit quindi esente dall applicazione della normativa PED 2014 68 UE Ri...

Page 3: ...3 LOCATION AND MINIMUM TECHNICAL CLEARANCES 14 7 4 DIMENSIONS 15 7 5 HYDRAULIC CONNECTIONS 15 7 5 1 Characteristics of water of the plant circuit 16 7 5 2 Hydraulic circuit type 16 7 5 3 Handbook 17...

Page 4: ...D PRESSURE OF THE UNIT WITH INTEGRATED CIRCULATOR 32 16 CIRCULATOR S CURVES 33 16 1 MODELS HPE 25 35 33 16 2 MODEL HPE 50 50F 33 16 3 MODEL HPE 60 34 16 4 MOD HPE 60 HPE 70 34 16 5 CIRCULATOR CHARACTE...

Page 5: ...g or transcription errors The customer must keep any updated copy of the manual or parts of it delivered by the manufacturer as an attachment to this manual The company is available to give any detail...

Page 6: ...ce s health and safety including 89 391 CEE 89 686 CEE 89 655 CEE 2009 104 CE 86 188 CEE and 77 576 CEE directives Every employer shall implement such norms and ensure that workers to respect them It...

Page 7: ...or each of the two components Respiratory protection For rescue and maintenance operation in storage tanks use self contained respirator The vapors are heavier than air and can cause suffocation by re...

Page 8: ...diameter is 7 94 mm the thickness of the aluminium fins is 0 12 mm The pipes are mechanically expanded into the aluminium fins in order to improve the heat transfer coefficient The geometry of this he...

Page 9: ...gy provide maximum efficiency regarding the standard units with scroll compressors The EVI technology consists of injecting the refrigerant vapour at the intermediate stage of the compression process...

Page 10: ...which identify the sizes versions and factory mounted accessories no 1 fixed digits equal to 0 for now it is not used 0110516 CT1 TA IV CI KA GI FAN SIL TR 00 MC FATHER CODE SIZE VERSION 0110516 CT T...

Page 11: ...Module not present 1 GI Module present 2 Modbus communication protocol 4 3 Modbus communication protocol and GI module present 0 DC fan 0 Not silenced 1 Silenced 2 Super silenced 0 Coil without treatm...

Page 12: ...provides thermo acoustic insulators on compressors 2 The super silenced unit with SSL accessory provides thermo acoustic insulators on compressors and a special diffuser installed on the fan which re...

Page 13: ...this manual can create dangerous situations After receiving the unit immediately check its integrity The unit left the factory in perfect condition any eventual damage has to be questioned to the car...

Page 14: ...CLEARANCES All i HP models are designed for outdoor installations any cover over the unit or locating near trees even if they partially cover the unit has to be avoided in order to allow the air recir...

Page 15: ...Make sure that when designing the pipe length and diameter do not exceed the maximum head loss on the plant side please see the technical data available head pressure WARNING An air vent valve should...

Page 16: ...h lack of washing of the system or lack tampering of the Y filter the company reserves the right not to pass the replacement of the component as a guarantee 7 5 1 Characteristics of water of the plant...

Page 17: ...ter on the charging topping up pipe must be suitably pre filtered from any impurities and suspended particles Make sure that you have installed a cartridge filter removable WARNING Before beginning th...

Page 18: ...CIRCULATOR ON BOARD UNIT M AXIAL FAN PV PRESSURE CHECK VALVE CP CAPILLARY SE OUTDOOR AIR TEMPERATURE SENSOR V ON OFF VALVE WITH SOLENOID 7 6 2 Refrigerant circuit of HPE 50 model EEV ELECTRONIC EXPANS...

Page 19: ...VERTER COMPRESSOR P CIRCULATOR ON BOARD UNIT M AXIAL FAN PV PRESSURE CHECK VALVE 7 6 4 Refrigerant circuit of HPE 50F model EEV ELECTRONIC EXPANSION VALVE NRV NO RETURN VALVE ST COMPRESSOR INLET TEMPE...

Page 20: ...TEMPERATURE INJP INJECTION PRESSURE TRANSDUCER INJ INJECTION VALVE 7 7 ELECTRICAL CONNECTIONS Check if the power supply circuit meets the unit s electric nominal data tension phases frequency reporte...

Page 21: ...not ground the unit with pipes or lightning rods A poor grounding of the unit can result in electrocution Warning Electrostatic discharges can damage the electronic components before performing any w...

Page 22: ...lectric box is opened i HP 0125 i HP 0135 i HP 0250F i HP 0250 On board terminal block and user s terminal block Support boards Transformer Driver board one for each inverter compressor Disconnecting...

Page 23: ...Ph N PE 400V 50Hz The power cables should be brought inside the electrical panel of the unit and connected to the disconnecting switch inside the electric panel itself in the bottom at the left as sho...

Page 24: ...tput 230Vac 50Hz 5A resistive 1A inductive 1 2 Secondary circulator GNDR Serial communication Modbus ground reference connection terminal for remote supervision R Serial communication Modbus signal co...

Page 25: ...l indications on unit labels are respected Check if all power cables are properly connected and all terminals are tightly fixed Check if the electrical connections are performed according to the norms...

Page 26: ...regarding the limits set out in Paragraph 20 4 Before you turn the unit on after a long off period make sure that the temperature of the mixture of water and glycol is higher than or at least equal t...

Page 27: ...to direct the water jet perpendicular to the surface of the condenser for not to bend the aluminum fins Avoid hitting the condenser with the water hose It is recommended not to place your thumb on th...

Page 28: ...ion 12 1 Residual risks In this paragraph we point out the most common situations that could give rise to risks that cannot be eliminated by the manufacturer during the design phase of the project Ris...

Page 29: ...98 1 97 Load losses user s side heat exchanger 4 kPa 33 46 28 Energetic class Water temp 35 C 55 C Classe A A A A A A Compressor Type Scroll DC Inverter Scroll DC Inverter Scroll DC Inverter Rfrigeran...

Page 30: ...ger 4 kPa 27 74 25 Energetic class Water temp 35 C 55 C Class A A A A A A Compressor Type Scroll DC Inverter Scroll ON OFF Scroll DC Inverter Scroll DC Inverter Rfrigerant oil type FVC68D FVC68D FVC68...

Page 31: ...W W 3 98 4 17 3 90 Water flow rate 1 L s 1 00 1 01 1 36 1 37 1 73 1 74 Load losses user s side heat exchanger 1 kPa 32 37 20 Heating Heating capacity 3 kW 24 15 24 02 32 50 32 36 47 78 47 58 Power inp...

Page 32: ...in apex 1 2 3 and 4 refer to the instantaneous power according to EN 14511 The declared data stated in the apex 6 is determined according to the UNI EN 14825 WARNING The minimum temperature allowed fo...

Page 33: ...circulator with the possibility of choice between constant P and variable P 16 2 MODEL HPE 50 50F Configuration with integrated circulator control via 0 10 volt analogic signal Configuration with auto...

Page 34: ...0 23 Because of the circulators have got similar prevalence curves to those integrated please refer to Paragraph 15 for plant designing 17 HEAD LOSS CURVES OF THE HYDRONIC CIRCUIT We obtain the press...

Page 35: ...1L s we obtaine 1 4kPa valve head loss 30kPa hydronic circuit head loss 34 9 kPa total internal head loss 19 ACCESSORIES TO REDUCE THE NOISE LEVEL 19 1 SL The silenced unit with SL accessory is provid...

Page 36: ...on systems the proper flow rate for getting the best performance from your unit can be found at maximum speed of the circulator using the pressure gauges for controlling the pressure difference betwee...

Page 37: ...30 C Water outlet temperature standard injection version Min 25 C Max 58 C 59 C Heat pump mode for sanitary hot water Ambient temperature standard injection version Min 15 25 C Max 50 38 C Ambient te...

Page 38: ...ater flow rate correction factor PDCF Pressure drops correction factor The water flow rate and pressure drop correction factors are to be applied directly to the values given for operation without gly...

Page 39: ...A2B ACCORRONI E G VIA ANCONA 37 60027 OSIMO AN www accorroni it a2b accorroni it...

Page 40: ...tolo puramente indicativo la A2B Accorroni E G S r l si riserva di apportare eventuali modi che senza alcun preavviso web site www accorroni it e mail a2b accorroni it A2B Accorroni E G s r l Via d An...

Reviews: