RI-130 Reader Interface Installation & User's Guide
J13 & J14 I
NPUT
C
ONNECTIONS
The RI-130 provides 12 input connections. Three connections are used for Door Open
Detect, Exit Push-button and Tamper Detect. The additional 9 points are user defined.
An open contact will have 20-24 VDC across it. A closed point will have approximately
10 mA of current. All of the input points for J14 are electrically common to ground.
Each input has an LED indicator, which will light when the input contact is closed.
Note:
A grounding connector is provided.
Any monitor point can be tied to alarms and conditional responses in the software.
Function
J14 – Pin #
Common
J13 – Pin #
LED
FED/DOD
Input 0
Pin #1
Pin #1
D7
Request To Exit
Input 1
Pin #2
Pin #2
D8
Tamper Detect
Input 2
Pin #3
Pin #3
D9
Input 3
Pin #4
Pin #4
D10
Input 4
Pin #5
Pin #5
D12
Input 5
Pin #6
Pin #6
D13
Input 6
Pin #7
Pin #7
D14
Input 7
Pin #8
Pin #8
D15
Input 8
Pin #9
Pin #9
D16
Input 9
Pin #10
Pin #10
D17
Input 10
Pin #11
Pin #11
D18
Input 11
Pin #12
Pin #12
D19
Door Open Detect
The Door Open Detect pin detects that the door is closed when the circuit is
closed.
Request To Exit
When the
exit push-button’s
circuit is completed with the Ground, both the Go
and the Shunt relay will fire. As long as the circuit is completed, the relays will
stay energized. After the circuit is opened, the relays will stay energized for their
respected times.
Tamper
The
Tamper
Detection message is reported when the RI-130 senses that the input
went from a closed state to an open state.
Page 4
©
Copyright 2009, Access Specialties International, LLC All Rights Reserved