RI-130 Reader Interface Installation & User's Guide
**Unlock and shunt time can be set from 1 to 255 seconds through the Access Gold or
ASI 2000 Software.
J5 H
OST
C
OMMUNICATIONS
J5 provides the connections for communications to the IC-1600 panel or a Channel
Expander (CE-1600). A Channel Expander multiplexes one channel on an IC-1600 into
an additional 16 ports and can be placed up to 2 miles away from the IC-1600.
Removable terminal blocks are provided for easy installation.
The RI-130 requires a 4-wire connection to the host. The cable should be 22 gauge,
shielded cable, consisting of 2 twisted pair, and all shields earth grounded at one end.
The maximum allowed distance from the RI-130 from the IC-1600 or CE-1600 is 2
miles.
Note:
The greater the distance, the greater the delay in transfer of data between the CC-
165 and the IC-1600.
Host (a channel or port)
J5 – RI-130 Lower Board
Data +
Pin #1
Data –
Pin #2
Pin #3
Enable –
Pin #4
Unused
Pin #5
J12 I
NSTALLING
A R
EADER
The RI-130 provides 6 wire connections for a reader. The cable length from the Reader
to the RI-130 should not exceed 500 feet. The cable should be 22 gauge, shielded cable,
consisting of 3 twisted pair, and all shields earth grounded at one end. The standard RI-
130 will read 26 or 27 bit card formats.
J12 – RI-130 Top Board
5 VDC
Pin #1
12 VDC
Pin #2
Ground
Pin #3
LED Control
Pin #4
Data 0 (Data –) Pin #5
Data 1 (Data +) Pin #6