BUFFER SETTING (LOW HUMIDITY TRIGGERS)
For Low Humidity Triggers, this buffer figure will
create a trigger-off point above your set trigger
point. For example, if you had set the Low Buffer
Trigger at 40% and set the Humidity Buffer at 6%.
Then your device will trigger on when it meets or
falls below 40%, and only trigger off when it rises
above 46%. The 46%F figure is obtained by taking
your Low Humidity Trigger of 40% and adding your
humidity buffer of 6%.
PROGRAMMING