29
PROGRAMMING
BUFFER SETTING (HIGH HUMIDITY TRIGGERS)
For High Humidity Triggers, this buffer figure will
create a trigger-off point below your set trigger
point. For example, if you had set a High Humidity
Trigger at 70% and set a Humidity Buffer at 4%.
Then your device will trigger on when it meets or
rises above 70%, and only trigger off when it falls
below 66%. The 66% figure is obtained by taking
your High Humidity Trigger of 70% and subtracting
your Humidity Buffer of 4%.