background image

22

EN/US/CA/A.mist A.mistT/UM-2239-1

Subject to alteration without prior notice.

FAULT TRACING

14

Mal-

function

Possible cause / 

Action

Low capacity

(air flow)

The fan rotates in the wrong direction.

Action: 

Check that the fan rotates according to the arrow on the motor 

(only skilled personnel).

With VFD (frequency converter): The fan speed is set too low.

Action: 

Check/adjust the fan speed (rpm/Hz) (only skilled personnel).

High pressure drop in the duct system.

Action: 

Measure the negative pressure in the filter unit’s inlet plenum (before filter stage 1) and 

compare with the “available external pressure drop” under “Technical data”. Check the damper 

adjustment. Is the duct system sized for the actual airflow and filter unit?
The filter cassettes are clogged.

Action: 

Check the pressure drop. If the yellow or red LED is lit for one of the filter stages, the 

cassette should be replaced.

Abnormally short service interval 

for filter stage 1:

Too much oil in the inlet plenum because of no or improper oil drainage from the filter unit.

Action: Make sure that drainage is provided for. Use one of the liquid traps described under 

“Accessories”.
Sticky and or solid particles form a face loading.

Action: Look at the position of the suction point in the machine. Is it possible to move or pro-

tect the inlet with a shield to decrease the amount of sticky and solid particles sucked into the 

filter unit? A pre-filter or spray system could also be a solution.
Chips and swarf is sucked in to the filter unit.

Action: Look at the position of the suction point in the machine. Is it possible to move or pro-

tect the inlet with a shield to decrease the amount of solid particles sucked into the filter unit? 

A pre-filter could also be a solution.
Poor drainage from the cassette because of high viscosity (sluggish liquid particles).

Action: 

If the fluid in the process has a high viscosity, it is necessary to add fluid with a spray 

system (see “Accessories”).

The pollution is too dry.

Action: Look at the position of the suction point in the machine. Is it possible to move it so that 

it sucks more liquid? 

A spray system could also be a solution.

If emulsion is used, the filter cassette may dry out as the water in it evaporates if the unit is 

running when production has stopped. 

Action:

 Switch off the filter unit when it is not in use.

Abnormally short service 

interval for filter stage 2 

or the HEP

A filter:

Too much oil in the inlet plenum because of no or improper oil drainage from the filter unit.

 

Action:

 

Make sure that drainage is provided for. Use one of the liquid traps described under 

“Accessories”.

Air leakage past the preceding filter stage(s) because of incorrectly positioned filter cassettes 

or damaged sealing strips. This results in unfiltered air reaching filter stage 2 / the HEPA filter.

Action: 

Check that filter stages 1 and 2 are locked in position. 

Check that the sealing strips of 

filter stages 1 and 2 are undamaged and facing upward. 
Particle overload because of a too high particle load (mg/m³) or too high fraction of small par

-

ticles. 

Action:

 Measure the particle load before the filter unit, after filter stage 1 and after filter stage 

2. Check with the guidelines if this filter unit is suitable for the application and if there are any 

options. Contact Absolent or your local distributor if you need advice.

Summary of Contents for A-mist6C

Page 1: ...EN US CA A mist A mistT UM 2239 1 User s Manual in original Oil Mist Filter A mist6C A mist10 A mist20 A mist60 A mist40T A mist40TF A mist80T A mist80TF EN A mis t US CA A mis T t...

Page 2: ...rting A mist40 80 6 5 5 Floor mounting 6 5 6 Installation 7 6 Operation Design 7 7 Technical Data 8 7 1 Technical data A mist6C A mist10 A mist20 A mist60 8 7 2 Technical data A mist40T TF 9 7 3 Techn...

Page 3: ...er unit Danger Heavy products The filter cassettes are heavy Check the weight of the relevant filter cassette before handling Particulars of their weight is located on the rating plate of the filter c...

Page 4: ...near the fan when operational These can be sucked into the fan or get caught Risk of tipping over Always check the weight of the filter unit technical data heading 7 before lifting When equipped with...

Page 5: ...cessary contact the shipper 5 2 Transporting A mist6C A mist10 A mist20 The filter unit is delivered on a wooden pallet and is wrapped in plastic foil A mist10 and A mist20 have a high centre of gravi...

Page 6: ...hem If they need to be lifted do so according to any of the following methods Fig 1 Use an overhead crane to lift the filter unit stan ding on a wooden pallet Fig 2 Use a fork lift to lift the filter...

Page 7: ...re properly secured when the re tainer arms point upwards If a filter cassette has become loose during the transport secure it and close the service door How to secure see 12 3 3 Connect the drainage...

Page 8: ...h mm inch 350 11 8 620 24 4 620 24 4 620 24 4 620 24 4 620 24 4 620 24 4 Std inlet connection mm inch 125 5 9 160 6 3 160 6 3 200 7 8 200 7 8 200 7 8 400 15 7 Std return oil connection inch R11 4 R11...

Page 9: ...9 Filter cassettes Main filter pc 4 4 Absolute filter HEPA pc 2 2 Performance Max airflow m h cfm 4000 2350 4000 2350 Noise level dB A 1 702 49 7 71 6 25 4 28 8 15 7 12 4 11 8 12 8 48 1 49 8 11 8 25 4...

Page 10: ...cfm 8000 4700 8000 4700 Noise level dB A 1 732 1 The noise level specified in the user s manual is applicable to filter units with external fan 2 The noise level specified has been measured at a dist...

Page 11: ...from the fan to the terminal blocks on the side of the filter unit Warning Dangerous voltage All electrical work must be carried out by qualified electricians Electrical data can be read from the rati...

Page 12: ...US CA A mist A mistT UM 2239 1 Subject to alteration without prior notice 8 3 Electrical connection of A monitor 230V 400V 460V 15 VDC o P max 230V 1A P P ELECTRICAL CONNECTION cont 8 Flow diagram A m...

Page 13: ...otation of the fan motor according to section 2 above If the unit is run with a too high flow there is a large risk that the life span of the filter cas settes will be shortened 4 Pressure drop over t...

Page 14: ...tage 2 Filter stage 1 A mist80T A mist40T CARE MAINTENANCE cont 10 1 In order to get to know your new installation the filter cassettes should be checked once a month during the first six months the f...

Page 15: ...OUR COUNTER DEVICE An hour counter device is also included in our standard equipment It measures and monitors the operation time in hours for the filter unit ALARM On the transformator card there is a...

Page 16: ...e filter cassette HANDLING THE FILTER CASSETTES 12 Warning Use requisite personal protection equipment when performing service work on the filter unit Lifts or the like must be used when carrying out...

Page 17: ...and No 2 centre can be washed several times Wash with water based degreasing agent in a chamber washer Figure C max permissible water tem perature 90 C 194 F After washing the filter must be left to d...

Page 18: ...ue to the normal subatmospheric pressure inside the filter unit It must fit tightly against the filter unit and it must be filled with liquid To be able to use this liquid trap the filter unit has to...

Page 19: ...top of the filter unit place the cover and fasten it with the enclosed bolts Outlet diameter 250mm Sound insolation hood A mist10 A mist20 A mist60 The sound insolation hood is used when there is a n...

Page 20: ...e instructions for use A mist filter units can be supplied with a mounted protective motor contactor The A mist filters unit can be equipped with a frequency converter with integrated pressure sen sor...

Page 21: ...nformation PREFILTER FOR SEVERE DIRT 13 8 STAND ALONE A MONITOR 13 9 A monitor is integrated at the front of nearly all A mist and A smoke filter units as standard With the stand alone A monitor it is...

Page 22: ...e Is it possible to move or pro tect the inlet with a shield to decrease the amount of solid particles sucked into the filter unit A pre filter could also be a solution Poor drainage from the cassette...

Page 23: ...rranty is however only valid if the product is in its original configuration and only when original spare parts have been used when servicing or repai ring the filter unit Some examples on why orignal...

Page 24: ...l documentation Technical writer Staplaregatan 1 SE 531 40 LIDK PING Sverige Tel 46 0 510 48 40 00 We Absolent AB declare under our sole responsibility that the product to which this declaration relat...

Page 25: ...NOTES...

Page 26: ...NOTES...

Page 27: ......

Page 28: ......

Reviews: