| Configuring the Wallbox eMH2 –
Stand-alone operation of a Slave wallbox
20
18
In the dialog box that pops up, click
OK
.
y
The new setting is now being transferred to
the wallbox.
y
The
Devices
field now shows the device
RFIDM60 - standalone CONFIG MODE
.
19
In the
Devices
field, click on the device
RFIDM60 - standalone CONFIG MODE.
20
Click the
Device specification > Leave config
mode
button.
21
In the dialog box that pops up, click
OK
.
y
The new setting is now being transferred to
the wallbox.
y
The
Devices
field now shows the device
RFIDM60 - standalone CONFIG MODE
.
22
Close the
Configuration Software
application using the
X
button in the top right corner of the application
window and click
OK
in the dialog box that pops up.
23
Disconnect the computer from the wallbox.
y
If connected via USB interface:
Unplug the USB extension cable from the USB
port in the wallbox and from your computer's
USB port.
y
If connected via LOMK218:
Disconnect the RS485-RJ12 adapter from the
spring terminals in the wallbox. You can also
unplug the USB-RS485 cable from the RS485-
RJ12 adapter and from your computer's USB
port.
A M B
CONTROL
A M B
METER
A M B
CONTROL
A M B
METER