ABL 3W2207 Installation Manual Download Page 14

preparatIons, InstallatIon and takIng Into operatIon

10

•  Depending on the desired rated power, the installation of the wallbox may need to be 

registered with and/or approved by the local electricity grid operator. Please consult the 

local regulations of your electricity grid operator.

•  Cable dimensions must be adjusted according to the desired rated power and other 

aspects (such as cable length, material, cabling method etc.). The terminal blocks in 

the wallbox are designed for cable dimensions of up to 16 mm

2

.

•  The power supply cables may be installed above or below the wall surface: The 

mounting plate provides alternative cable inlets at the top and at the rear.

•  The power supply for the wallbox must always be protected by anMCB: Please 

always observe the applicable national regulations regarding the selection of the 

MCB. 

•  The wallbox does not have a dedicated ON/OFF switch: If you want to take the 

wallbox out of operation, you must always switch the upstream domestic MCB and 

the internal RCCB(s) to the 

0

 (OFF) position. In addition, you have the option of de-

activating the charging function of the 

eMH3

 via the integrated RFID module: The 

necessary procedure is described in section “Deactivating and reactivating of the 

charging function via RFID” on page 14 of the user manual for the ABL Wallbox.

•  Please always ensure that the installation requirements listed in this manual are 

complied with. Disregard or actions to the contrary may lead to severe injury by elec-

tric shock or even death. In addition, in case of contravention of the notices given, 

the proper operation of the wallbox cannot be guaranteed.

Mechanical and electrical installation

After determining the mounting site for the wallbox, you can begin with the installa-

tion. For installation you will need the following components:
•  Power drill or cordless drill (not included)
•  Drill bit Ø 10 mm, appropriate for the wall substrate (not included)
•  Screwdriver with flat head (2.5 mm blade width), Phillips head (PH1) and torx head 

(TX40, TX25, TX20, TX10) bits

•  Mounting plate (included)
•  Pliers or cutter for breaking or cutting out the cable inlet in the mounting plate (not 

included)

•  Four 8 x 60 wafer head (TX40 bit) screws for fixing the mounting plate (included)
•  Four 6 x 25 (TX25 bit) screws for fixing the wallbox housing to the mounting plate 

(included)

•  If required: Wall plugs suitable for the mounting substrate (included: 10 x 50 nylon 

wall plugs)

•  Spirit level if required (not included)

Summary of Contents for 3W2207

Page 1: ...VERSION EMH3 2016 10 28 IM ARTICLE NO 0301592 Installation manual Wallbox eMH3...

Page 2: ...Bayerische Elektrozubeh r GmbH Co KG Albert B ttner Stra e 11 91207 Lauf Pegnitz Germany Phone 49 0 9123 188 0 Fax 49 0 9123 188 188 Web www abl de Mail info abl de Customer Support Phone 49 0 9123 18...

Page 3: ...eration 6 Introducing the product 6 Unpacking and components included 6 Identifying your model variant 7 General requirements of the installation site 8 Requirements for the power supply 9 Mechanical...

Page 4: ...cations 23 Scale drawings and dimensions 25 Contact chartType 1 Type 2 27 Guidelines Norms 27 CE certification and compliance declaration 28 Glossary Definitions 28 Trademarks 28 Intellectual Property...

Page 5: ...charging socket and 22 kW max output 3W2209 eMH3 Single with charging socket and shutter 22 kW max output 3W2214 eMH3Twin with charging sockets and 2 x 11 kW or 1 x 22 kW max output 3W2217 eMH3 Twin...

Page 6: ...care PLEASE NOTE Sections marked with this symbol draw attention to further important in formation and special features that are necessary for the reliable operation of the device Actions marked with...

Page 7: ...d at all times No liquids or objects or receptacles containing liquids must be placed on the hous ing Please note that additional overvoltage protection may be required depending on the connected vehi...

Page 8: ...tact ABL technical support Always contact ABL technical support if the housing has been damaged mechanically the housing cover has been removed or can no longer be closed or locked sufficient protecti...

Page 9: ...allbox should not be installed in areas of high pedestrian traffic Installation along thoroughfares and marked escape routes should be especially avoided Never install the wallbox in a confined space...

Page 10: ...ng cover allow you to check the current operating status at any time Should a malfunction occur you can identify the cause by its specific LED error code without having to open the housing After being...

Page 11: ...32 A Single charging station with fixed charging cable according to IEC 62196 2 Type 2 integrated factory deactivated RFID module for access control internal Type A RCCB internal DC fault current dete...

Page 12: ...rging station with two integrated charg ing sockets according to IEC 62196 2 Type 2 with locking mechanisms for separately avail able charging cables Type 2 to Type 2 or Type 2 to Type 1 integrated fa...

Page 13: ...gineered for operation in high ambient tempera tures However it must be ensured that the maximum operating temperature is not exceeded through external influences such as direct sunlight or similar Th...

Page 14: ...integrated RFID module The necessary procedure is described in section Deactivating and reactivating of the charging function via RFID on page 14 of the user manual for the ABL Wallbox Please always e...

Page 15: ...r even death Proceed as follows to drill the holes using the mounting plate 1 Ensure that a sufficiently dimensioned power supply is available at the desired instal lation site Otherwise a power suppl...

Page 16: ...inserted into the connection area from above and can be fixed using its allocated strain relief PLEASE NOTE The strain relief is not required if the power supply enters from the rear 83 7 Now open th...

Page 17: ...into the respective opening in the mounting plate this already protects the wallbox from falling 11 Now fix the wallbox to the mounting plate using the screwdriver TX25 bit and the four 6 x 25 screws...

Page 18: ...onnected as follows DESIGNATION CONNECTION CODING Current carrying conductor phase 1 L1 Current carrying conductor phase 2 L2 Current carrying conductor phase 3 L3 Neutral N Protective earth PE The tw...

Page 19: ...rovide a lower or higher charging current the preset current for the wall box must be adjusted accordingly before you replace the electronic components cover and then take the wallbox into operation P...

Page 20: ...ical installation you must check the correct functioning of the ABL Wallbox for operation and resolve any malfunctions or installation errors that may have occurred Proceed as follows to take the ABL...

Page 21: ...Possible cause Suggested solution LEDs are not functioning The wallbox does not have a power supply First check the internal RCCB s Should power be interrupted in the domestic supply Check the upstre...

Page 22: ...cted a disallowed operat ing state during the initial or periodic self test The green LED flashes three times then the blue LED flashes once the red LED is continuously ON Solution In both cases switc...

Page 23: ...ashes twice then the blue LED flash es twice the red LED is continuously ON Solution The wallbox automatically reinitiates the charging procedure every 60 sec onds Should the error continue to occur c...

Page 24: ...current The green LED flashes four times every fourth time the blue LED also flashes the red LED is continu ously ON Solution The wallbox automatically reinitiates the charging procedure every 60 sec...

Page 25: ...of operation see Tak ing the product out of and back into operation on page 22 and contact the special ist electrical contractor who has performed the installation to resolve the error 200 ms 200 ms...

Page 26: ...installation of the eMH3 must always be carried out by a qualified electrical contractor To take the wallbox into operation again at a later time please proceed as follows 1 Switch on the upstream MC...

Page 27: ...ection devices Type A 30 mA RCCB and DC RCM I n d c electronic DC fault current detector 6 mA Control Customization Internal RS485 and USB interfaces no user access Operating temperature 30 C to 50 C...

Page 28: ...cc with IEC62196 2 2 pcs Circuit protection devices Type A 30 mA RCCB and DC RCM I n d c electronic DC fault current detector 6 mA Control Customization Internal RS485 and USB interfaces no user acces...

Page 29: ...awings and dimensions The ABL Wallbox is delivered fully assembled and quality checked All measurements in the following elevations are in mm Mounting plate and wallbox Wallbox 3W2205 200 254 83 477 9...

Page 30: ...Appendix 26 Wallboxes 3W2207 and 3W2209 Wallboxes 3W2214 3W2217 and 3W4401 194 400 492 134 194 400 492 134...

Page 31: ...ive charging systems for electric vehicles Part 1 General requirements IEC TS 61439 7 2014 Part 7 Switching device combinations for specific applications such as marinas campgrounds market squares cha...

Page 32: ...or download Glossary Definitions In the following important abbreviations and terms used in this manual are explained Abbreviation Description Meaning DC Direct Current Direct current DC RCM Direct Cu...

Page 33: ...ossible misinformation contained in these instructions This manual in its entirety or in parts must not be reproduced stored electronically or otherwise transmitted electronically electrically mechani...

Page 34: ...Albert B ttner Stra e 11 D 91207 Lauf Pegnitz Ph 49 0 9123 188 0 Fax 49 0 9123 188 188 info abl de www abl de ABL SURSUM Bayerische Elektrozubeh r GmbH Co KG MADE IN GERMANY...

Reviews: