Make sure that the installation room (spaces,
divisions and ambient) is suitable for the
electrical apparatus
•
Check that all the installation, putting into
service and maintenance operations are carried
out by quali
fi
ed personnel with suitable
knowledge of the apparatus
•
Make sure that the standard and legal
prescriptions are complied with during
installation, putting into service and
maintenance, so that installations according
to the rules of good working practice and safety
in the work place are constructed
•
Strictly follow the information given in this
instruction manual
Dangerous
Pay special attention to the danger notes indicated
in the manual by the following symbol
•
Check that the rated performance of the
apparatus is not exceeded during service
•
Check that the personnel operating the
apparatus have this instruction manual to
hand as well as the necessary information
for correct intervention
•
Responsible behavior safeguards your own
and others’ safety
For any requests, please contact the ABB Assistance Service.
Fundamental notes on this manual:
Read the relevant sections of this manual through
in full before performing work, so as to ensure
correct handling.
Paragraphs in this manual are marked in
accordance with their significance. The markings
mean the following:
Hazard warning, meaning in this manual
that death or serious injury and
considerable damage may occur if the
actions described are not performed.
Important note, meaning in this manual
that injury and damage may occur if the
actions described are not performed.
Attention is drawn to further documents.
Note on safety
This internal arc classification to IEC 62271-200
confirms a tested degree of operator protection.
The information on accessibility of the switchgear
as required by IEC 62271-200 can be found on
the type plates of the panels.
The coding is as follows:
A: Switchgear installed in closed rooms with
access restricted to authorised personnel
F: Accessibility from the front (F = Front)
L: Accessibility from the sides (L = Lateral)
R: Accessibility from the rear (R = Rear)
Instructions to be stipulated by the
operator of the switchgear must prevent
access by personnel to non-arc
classified areas.
The switchgear is not safe for personnel
under the terms of IEC 6227-200 when
•
the covers on the cable termination
compartment are not properly fitted, or
•
the switchgear is operated without end covers
Operator protection in accordance with IEC
62271-200 presupposes that the distances we
prescribe between the switchgear and the
walls and ceiling of the switchgear room.
—
For your safety!