Commissioning
Product manual 2TMD041800D0002
│
148
8.8
Alarm settings
8.8.1
Alarm zone connection
1. Connect normally closed detectors
2. Connect normally open detectors
10K
Resister
Detector(1)
GND
Z(n)
10K
Resister
Detector(1)
GND
Z(n)
Z(n): Designated alarm zone connector on the indoor station
Detector(2) Detector(n)
Connect one detector
Connect multiple detectors
10K
Resister
Detector(1)
GND
Z(n)
10K
Resister
GND
Z(n)
Z(n): Designated alarm zone connector on the indoor station
Connect one detector
Connect multiple detectors
Detector(1)
Detector(2)
Detector(n)