11
General characteristics of circuit-breakers with right lateral operating mechanism for
UniMix type switchgear (12 – 17.5 – 24 kV)
VD4/UniMix 12
12
12
28
75
50-60
630
12.5
16
20
25
12.5
16
20
25
31.5
40
50
63
40…60
10...15
50…75
50...70
700
(4)
- 734
(5)
382 (IP30) - 393 (A.I.)
1030
230
65
40 - 80 - 250 - 1250
(2)
(3)
1VCD000106
(4)
1VCD000107
(5)
1VCD400097
(4)
1VCD400098
(5)
- 5 ... + 40
VD4/UniMix 17
17.5
17.5
38
95
50-60
630
12.5
16
20
25
12.5
16
20
25
31.5
40
50
63
40…60
10...15
50…75
50...70
700
(4)
- 734
(5)
382 (IP30) - 393 (A.I.)
1030
230
65
40 - 80 - 250 - 1250
(2)
(3)
1VCD000106
(4)
1VCD000107
(5)
1VCD400097
(4)
1VCD400098
(5)
- 5 ... + 40
VD4/UniMix 24
24
24
50
125
50-60
630
12.5
16
20
—
12.5
16
20
—
31.5
40
50
—
40…60
10...15
50…75
50...70
700
(4)
- 734
(5)
382 (IP30) - 393 (A.I.)
1030
230
65
40 - 80 - 250 - 1250
(2)
(3)
1VCD000106
(4)
1VCD000107
(5)
1VCD400097
(4)
1VCD400098
(5)
- 5 ... + 40
(1) For circuit-breakers with PR 521 device and 3 current sensors, increase the weight indicated by 20 kg
(2) Rated current of the current sensors (the PR521 device and the current sensors are optional)
(3) DK type phase current sensors on board the circuit-breaker and DK type toroidal CT not on board (the PR521/DK device and the DK sensors are optional)
(4) VD4/UniMix-F for P1/F Unit (fixed circuit-breaker without wheels and cabled to terminal box)
(5) VD4/UniMix-R for P1/F Unit (fixed circuit-breaker with wheels and power cord with plug)
H
Circuit-breaker
Standards
IEC 62271-100
CEI 17-1
(file 1375)
Rated voltage
Ur
[kV]
Rated insulation voltage
Us
[kV]
Withstand voltage at 50 Hz
Ud
(1 min) [kV]
Impulse withstand voltage
Up
[kV]
Rated frequency
fr
[Hz]
Rated normal current (40°C)
Ir
[A]
Rated breaking capacity
Isc
[kA]
(rated symmetrical short-circuit current)
Rated short-time withstand
Ik
[kA]
current (3s)
Making capacity
Ip
[kA]
Operation sequence
[ O - 0.3s - CO - 15s - CO ]
Opening time
[ms]
Arcing time
[ms]
Total breaking time
[ms]
Closing time
[ms]
Overall
H
[mm]
dimensions
W
[mm]
(maximum)
D
[mm]
Pole centre distance
I
[mm]
Weight
(3)
[kg]
Application of PR521 protection device
In
[A]
Application of PR521/DK protection device
Table of standardised dimensions
Electric circuit diagram
Operating temperature
[°C]
Tropicalization
IEC:
60068-2-30, 60721-2-1
Electromagnetic compatibility
IEC
60694
W
D