10
General characteristics of circuit-breakers with right lateral operating mechanism for
ABB UniSwitch type switchgear (12 – 17.5 – 24 kV)
VD4/S 12
12
12
28
75
50-60
630
800
1250
12.5
12.5
12.5
16
16
16
20
20
20
25
25
25
12.5
12.5
12.5
16
16
16
20
20
20
25
25
25
31.5
31.5
31.5
40
40
40
50
50
50
63
63
63
40…60
10...15
50…75
50...70
730
282
990
210
67
40 - 80 - 250 - 1250
(2)
see note
(3)
1VCD000098
1VCD400098
- 5 ... + 40
VD4/S 17
17.5
17.5
38
95
50-60
630
800
1250
12.5
12.5
12.5
16
16
16
20
20
20
—
—
—
12.5
12.5
12.5
16
16
16
20
20
20
—
—
—
31.5
31.5
31.5
40
40
40
50
50
50
—
—
—
40…60
10...15
50…75
50...70
730
282
990
210
67
40 - 80 - 250 - 1250
(2)
see note
(3)
1VCD000098
1VCD400098
- 5 ... + 40
VD4/S 24
24
24
50
125
50-60
630
800
1250
12.5
12.5
12.5
16
16
16
20
20
20
—
—
—
12.5
12.5
12.5
16
16
16
20
20
20
—
—
—
31.5
31.5
31.5
40
40
40
50
50
50
—
—
—
40…60
10...15
50…75
50...70
730
282
990
210
67
40 - 80 - 250 - 1250
(2)
see note
(3)
1VCD000098
1VCD400098
- 5 ... + 40
W
H
D
(1) For circuit-breakers with PR 521 device and 3 current sensors, increase the weight indicated by 20 kg
(2) Rated current of the current sensors (the PR521 device and the current sensors are optional)
(3) Special version with “ß = 1” or “ß = 1, RI” curves for the Belgian market: please ask ABB for availability and delivery times
Circuit-breaker
Standards
IEC 62271-100
CEI 17-1
(file 1375)
Rated voltage
Ur
[kV]
Rated insulation voltage
Us
[kV]
Withstand voltage at 50 Hz
Ud
(1 min) [kV]
Impulse withstand voltage
Up
[kV]
Rated frequency
fr
[Hz]
Rated normal current (40°C)
Ir
[A]
Rated breaking capacity
Isc
[kA]
(rated symmetrical short-circuit current)
Rated short-time withstand
Ik
[kA]
current (3s)
Making capacity
Ip
[kA]
Operation sequence
[ O - 0.3s - CO - 15s - CO ]
Opening time
[ms]
Arcing time
[ms]
Total breaking time
[ms]
Closing time
[ms]
Overall
H
[mm]
dimensions
W
[mm]
(maximum)
D
[mm]
Pole centre distance
I
[mm]
Weight
(3)
[kg]
Application of PR521 protection device
In
[A]
Application of PR521/DK protection device
Table of standardised dimensions
Electric circuit diagram
Operating temperature
[°C]
Tropicalization
IEC:
60068-2-30, 60721-2-1
Electromagnetic compatibility
IEC
60694