57
Dismantling of Operating Coils Setup
Steps For Replacement of Motor 15032
(2)
Release the return spring, raise the pair of charging
pawls and push the lever towards (4).
(4)
Unscrew the motor flange fixing screws (6)
(6)
Raise the pair of driving latches using
screwdriver and push the lever (3) forward.
(3)
Remove the two motor limit microswitch
fixing screws (2)
Fig. 10
Steps For Replacement of Shunt Opening Release (YO2) 15030
Operating Coil Set-Up for Temperature –10 deg. C
Fig. 9