ENGINEERING
ETHERNET
1VLG5 00007 E
67
3.5.5
Naming convention to identify protection relays
The protection relay name must be unique within the planned network. A default name is
applied if it is not specified by the client and it is based on the reference designation system
of IEC 61346
–
Substation
3 characters
–
Voltage Level
1 character
•
B
> 420kV
•
C
< 380, 420> kV
•
D
< 220, 380) kV
•
E
< 110, 220) kV
•
F
< 60, 110) kV
•
G
< 45, 60) kV
•
H
< 30, 45) kV
•
J
< 20, 30) kV
•
K
< 10, 20) kV
•
L
< 6, 10) kV
•
M
< 1, 6) kV
•
N
< 1 kV
–
Voltage Level Index
1 character
–
Bay
3 characters, 1
st
char. = letter, 2
nd
-3
rd
char. = digits
–
Protection Relay
2 characters
For example,
S
ubstation
V
oltagelevel
V
oltagelevelindex
B
ay
P
rotectionRelay
SUBJ1J01A1
3.5.6
IP address allocation
The IP address is a number that identifies a network device. Each device connected to a net-
work must have a unique address. The default IP address range for a substation is: 172.16.X.X -
172.30.X.X. The IP addresses and IP masks are a specific feature of each device. In case of
device failure, the replacement device receives the same IP address. The IP address should be
structured in a way to reflect the physical plant layout according to IEC 61850-90-4.
–
172.
NET.BAY.DEVICE
Subnet mask 255.255.0.0 (Class B)
–
NET
•
16 - 30
16 = the highest voltage level,
17 = the second highest voltage level …
–
BAY
•
0
Station level (PC, COM600S, Satellites reference clock ...)
•
1-169
Bays
•
170 - 179
Virtual bays (substitution of actual devices by simulation or calculation)
•
201 - 250 Station Level Ethernet Switches
–
DEVICE
•
0
Bay Level Ethernet Switch
•
1- …
Protection relays
Note: PRP redu100
Summary of Contents for UniGear Series
Page 1: ... DISTRIBUTI ON SOLUTIONS UniGear Family UniGear Digital Engineering Guide ...
Page 2: ......
Page 3: ... DISTRIBUTI ON SOLUTIONS UniGear Family UniGear Digital Engineering Guide ...
Page 6: ......
Page 10: ......
Page 12: ......
Page 84: ...72 1VLG5 00007 E Figure94 VirtualLANs allocation in HSR PRP networks ...
Page 111: ......
Page 112: ... Visit us www abb com mediumvoltage Document Number 1VLG500007 Rev E ...