UNIGEAR DIGITAL
S ENS O RS
1VLG5 00007 E
7
2.1.2
Voltage sensors
Voltage measurement in the KEVA sensor is based on the resistive divider principle. Voltage
sensors are designed to be compact and shaped as support insulators. They can be installed
in the switchgear´s cable compartment or directly in the busbar compartment.
KEVA 17.5 B20
KEVA B sensor can be used in all applications up to the voltage level 17.5 kV. The sensor fulfils
requirements of accuracy class 0.5 for measurement purposes and accuracy class 3P for
protection purposes.
Figure 5: Voltage sensor KEVA 17.5 B20
Technical parameters
–
Rated primary voltage
15 /
3 kV
–
Rated power frequency withstand voltage
38 (42) kV
–
Rated lightning impulse withstand voltage
95 kV
–
Transformation ratio
10 000: 1
–
Accuracy class
0.5 / 3P
Summary of Contents for UniGear Series
Page 1: ... DISTRIBUTI ON SOLUTIONS UniGear Family UniGear Digital Engineering Guide ...
Page 2: ......
Page 3: ... DISTRIBUTI ON SOLUTIONS UniGear Family UniGear Digital Engineering Guide ...
Page 6: ......
Page 10: ......
Page 12: ......
Page 84: ...72 1VLG5 00007 E Figure94 VirtualLANs allocation in HSR PRP networks ...
Page 111: ......
Page 112: ... Visit us www abb com mediumvoltage Document Number 1VLG500007 Rev E ...