ENGINEERING
ETHERNET
1VLG5 00007 E
79
3.5.10.2
Time Settings <Mandatory>
Time / PTP / Global
PTPv2 must be configured in case SMV (IEC 61850-9-2LE) is used.
Operation IEEE 1588 / PTP = ON
Configuration IEEE 1588 / PTP / PTP Version-Mode
–
V2-transparent-clock; used only to correct and forward PTP messages. The device cannot
become a PTPv2 master.
Figure 103: PTP Global dialog
Time / PTP / Version 2(TC) / Global
Profile Presets / Profile = Power - Defaults
Operation IEEE 1588 / PTPv2 TC
–
Delay mechanism = P2P (Peer to Peer)
–
Primary Domain = 0
–
Network protocol = IEEE 802.3
–
Syntonize = enabled to synchronize also local time
–
Power TLV Check = enabled
–
VLAN = 1
Figure 104: PTP Version 2 (Transparent Clock) Global dialog