Electronic Overload Protection
The UMC protects single - and three-phase AC motors in compliance with IEC 60947-4-1. The tripping class can be set to class 5, 10,
20, 30 or 40. The advanced thermal motor model considers both the copper and iron parts of the motor thus providing the best
protection of the motor.
Before an overload trip actually happens, a pre-warning can be generated. During high overload situations the prewarning might
be raised just a few seconds before the actual trip happens.
The presently used
thermal capacity (0...100 %) of the motor is available to the user and thus a prediction of the
time to trip for the
current load situation. If the motor is switched off the time to trip shows 6553 sec (never trips). If the motor is running the predic-
ted trip time is updated regularly. The smaller the value the earlier the trip happens.
After an overload trip, the remaining cooling down time (=time to restart) is calculated regularly and also available to the user.
The motor can be restarted if the cooling time is 0 sec.
Block Diagram:
—
Signal flow of the thermal overload protection
The thermal information of the motor is cyclically stored (thermal memory) 1). After a thermal overload trip the motor must cool
down before it can be started again. There are two options to define the necessary duration of the cooling time.
• Fixed cooling time:
The user has to specify a fixed duration e.g. 15 minutes. After a thermal overload trip a further motor start is inhibited for that time.
The time that has to be adjusted depends on:
Motor size, motor with or without ventilation, the environment temperature etc. Considering these points the appropriate cool-
ing time can be estimated.
Some examples of motor cooling time constants (t.c.) (motor standstill) can help:
Size
1 kW - 1 pole
5 kW -1 pole
5 kW - 2 pole
20 kW - 2 pole
20 kW - 3 pole
100 kW - 3 pole
c.t.
10 min
15 min
20 min
30 min
40 min
70 min
•
Thermal capacity based cooling: The user specifies to which level (e.g. 60%) the thermal load level must drop before a motor start
is possible again.
1)
If the UMC was switched off while the cooling time was running and the power down time was shorter than 20 min, the UMC restarts the cooling timer with the
remaining cooling time.
Otherwise the cooling time is set to zero.
38
U MC10 0. 3 U N IVE R SA L MOTOR CONTROLLE R
T EC H N I C A L D E S C R I P T I O N
Summary of Contents for UMC100.3
Page 1: ... MANUAL Univeral Motor Controller UMC100 3 ...
Page 159: ...159 ...