General
Tightening torque for the input, output and supply terminals
Net weight
0.22 kg
Degree of protection
IP20
Temperature range
storage -25 ... +70 °C
operation 0 ... +55 °C (DX122-FBP.0) / +60 °C (DX111-FBP.0)
Marks, Approvals
CE, cUL, CCC, EAC
Relay Outputs
Number of relay outputs
4
1DO1, 1DO2 with root 1DOC
2DO3, 2DO4 with root 2DOC
Voltage range of contacts
12-250 V AC/DC
Uimp
4 kV
Short-circuit protection
6 A gG per root (1DOC, 2DOC)
Lowest switched power for correct signals
1 W or 1 VA
Switching of inductive power
Inductive loads need additional measures for spark suppression. Diodes for DC
voltage and varistors / RC elements for AC voltage are suitable. Some DC coil
contactors contain rectifiers which suppress sparks perfectly.
Switching capacity per relay contact acc. to EN 60947-5-1
(electromagnetic load)
AC-15 240 V AC: max. 1,5 A
AC-15 120 V AC: max. 3 A
DC-13 250 V DC max. 0.11 A
DC-13 125 V DC max. 0.22 A
DC-13 24 V DC max. 1 A
Relay contact service life
Mechanical 500 000 switching cycles
Electrical (250 V AC):
0.5 A: 100 000 cycles
1.5 A 50 000 cycles
Internal clearance and creepage distances of relay
contacts to 24 V circuits
> 5.5 mm (safety insulation up to 250 V AC)
(EN 60947-1, Pollution degree 2)
Pollution degree terminals: 3
ø 4,5 mm / 0.177 in / PH 1
2 x 0.5 ... 4 mm
2
2 x 20 ... 12 AWG
2 x 0.75 ... 2.5 mm
2
2 x 18 ... 14 AWG
2 x 0.75 ... 2.5 mm
2
2 x 18 ... 14 AWG
7mm
0.28 in
7mm
0.28 in
7mm
0.28 in
0.6 ... 0.8 Nm
5.31 ... 7.08 in.lb