Parameter Organisation
The UMC parameters are described in groups reflecting the major function blocks of the UMC. The figures in braces (e.g. 1.1) pro
-
vide the link the menu structure i.e. where it is displayed.
• Motor Management lists all parameters related to motor management i.e. starting and stopping the motor and the control function
•
Protection lists all parameters related to the motor itself (e.g. nominal current) and the motor protection functions
• Communication lists parameters related to the fieldbus communication
•
IO Module lists all parameters related to the optional IO expansion modules
•
Display lists all parameters directly related to the LCD panel
• Function block lists all parameters related to a specific function block.
The column "Adjustable via" shows the possible options to adjust a parameter. "All" means the parameter can be set via UMC100-
PAN, GSD-PDP32 (includes PROFINET), EDS DeviceNet and PBDTM. Otherwise the available options are listed.
Motor Management Parameters
Parameter
Number
Parameter
Description, Explanations
Options
Adjustable via
General motor management parameters
20
Control function
Defines the type of starter function
Transparent (1),
Overload relay (2),
Direct starter (3)
,
Reverse starter (4)
Star-delta starter (5),
Pole-changing starter (7),
Actuator_1 (9),
Actuator_2 (10),
Actuator_3 (11),
Actuator_4 (12)
Softstarter (13)
All
21
Rev lock-out time
Interlocking time before a start command in the opposite
direction is accepted
1-255 s
All
24
YD changeover
mode
The UMC switches from star to delta either after a defined time
or if the motor current has decreased to 90% of I
e1
Time (0),
Current (1)
All
25
YD starting time
(Time Limit
Actuator)
Time switching from star to delta. If the changeover mode is set
to 'current' this time defines when the motor current must be
below 90% of Ie. Set this parameter to at least 1s.
Defines the maximum travel time from one end position to the
opposite end position.
1s to 360s in steps of 0,1s.
Default: 60s
Unscaled: 10 ... 3600
Example: A value of 10 means
1s
All
26
Resistive Load
Other than motor load connected
No (0) / Yes (1)
All
27
Fault output
Behaviour of DO2 or DO3 in the event of a trip or fault.
Off (0)
,
Flashing DO2 (1),
On DO2 (2),
Invert DO2 (3),
Flashing DO3 (4),
On DO3 (5),
Invert DO3 (6)
All
47
Number of phases
Change from three phases to single phase load
3 Phases (3)
1 Phase (1)
All
22
Checkback
Selection of the checkback supervision method.
Contact DI0 (1),
Current (2)
,
Simulation (3)
All
86
Inching DI start
input (Jog)
Enables inching (i.e. jogging) of the start signal originating from
a digital input.
No (0)
,
Yes (1)
All
19
Enable custom
logic
Enable the execution of a customer defined application
No (0)
,
Yes (1)
All
123
PA R A M E T ER S A N D DATA S T R U C T U R E S O N A FI EL D B US