Parameter descriptions
82
TZIDC, TZIDC-110, TZIDC-120
42/18-84-EN
11.2.2 Parameter description
w
Parameter
Display
Function
Parameter
Unit
Factory setting
Customer
setting
P1._
STANDARD
P1.0 ACTUATOR
Actuator type
LINEAR, ROTARY
---
LINEAR
P1.1 AUTO_ADJ
Auto adjust
Function ---
---
---
P1.2 TOL_BAND
Tolerance band
0,30 … 10,00
%
0,30
P1.3 DEADBAND
Dead band
0,10 … 10,00
%
0,10
P1.4 TEST Test
Function ---
---
---
P1.5
1)
ADRESS
Busadresse
1 … 126
---
126
---
P1.6 EXIT Return to operat. level
Function ---
---
---
P2._
SETPOINT
P2.0
---
---
---
P2.1
---
---
---
P2.2 CHARACT
Characteristic curve
LINEAR, EP 1:25, 1:50, 25:1, 50:
1,USERDEF
--- LINEAR
P2.3 ACTION
Action of the output
DIRECT, REVERSE
---
DIRECT
P2.4 SHUT-CLS
Shut-off range 0%
OFF, 0,1 … 45
%
off
P2.5 RAMP^
Set point ramp, up
OFF, 0,1 … 999,9
sec
off
P2.6 RAMP
ˇ
Set point ramp, down
OFF, 0,1 … 999,9
sec
off
P2.7 SHUT-OPN
Shut-off range 100%
OFF, 80.0 … 100
%
off
P2.8 EXIT Return to operat. level
Function ---
---
---
P3._
ACTUATOR
P3.0 MIN_RGE
Min. of operating range
0,0 … 100,0
%
0,0
P3.1 MAX_RGE
Max. of operating range
0,0 … 100,0
%
100,0
P3.2 ZERO_POS
Zero position
CLOCKWISE, CTCLOCKWISE
---
CTCLOCKWISE
P3.3 EXIT Return to operat. level
Function ---
---
---
P4._, P.5_
---
---
---
P6._
MAN_ADJ
P6.0 MIN_VR
Min. operating range
0,0 … 100,0
%
0,0
P6.1 MAX_VR
Max. operating range
0,0 … 100,0
%
100,0
P6.2 ACTUATOR
Actuator type
LINEAR, ROTARY
---
LINEAR
P6.3 SPRNG_Y2
Spring action (Y2)
CLOCKWISE, CTCLOCKWISE
---
CTCLOCKWISE
P6.4 ADJ_MODE
Auto adjust mode
FULL, STROKE, CTRL_PAR, ZE
RO_POS, LOCKED
--- FULL
P6.5 EXIT Return to operat. level
Function ---
---
---
P7._
CTRL_PAR
P7.0 KP^ KP value, up
1,0 … 100,0
---
1,0
P7.1 KPv KP value, down
1,0 … 100,0
---
1,0
P7.2 TV
^ TV value, up
0 … 1000
msec
100
P7.3 TVv TV value, down
0 … 1000
msec
100
P7.4 GOPULSE^
Go pulse, up
0 … 200
msec
0
P7.5 GOPULSEv
Go pulse, down
0 … 200
msec
0
P7.6 Y-OPFSET^
Y offset, up
Y-Min … 100,0
%
40,0
P7.7 Y-OFFSETv
Y offset, down
Y-Min … 100,0
%
40,0
P7.8
---
---
---
P7.9 TOL_BAND
Tolerance band
0,30 … 10,00
%
0,8
P7.10 TEST Test
Function ---
---
---
P7.11 EXIT Return to operat. level
Function ---
---
---
P8._, P9._,
P.10_
---
---
---
P11._
FS/IP
P11.0 FAIL_POS
Save position selection
ACTIVE, INACTIV
---
INACTIV
P11.1 FACT_SET
Factory setting
Function ---
---
---
P11.2 IP_TYP
I/P module type
NO_F_POS,F_SAFE_1, F_SAF
E_2, F_FREEZE1, F_FREEZE2
--- NO_F_POS
P11.3 EXIT Return to operat. level
Function ---
---
---
1) only TZIDC-110
Summary of Contents for TZIDC
Page 57: ...Ex relevant specifications 42 18 84 EN TZIDC TZIDC 110 TZIDC 120 57 ...
Page 58: ...Ex relevant specifications 58 TZIDC TZIDC 110 TZIDC 120 42 18 84 EN ...
Page 59: ...Ex relevant specifications 42 18 84 EN TZIDC TZIDC 110 TZIDC 120 59 ...
Page 67: ...Ex relevant specifications 42 18 84 EN TZIDC TZIDC 110 TZIDC 120 67 ...
Page 68: ...Ex relevant specifications 68 TZIDC TZIDC 110 TZIDC 120 42 18 84 EN ...
Page 76: ...Ex relevant specifications 76 TZIDC TZIDC 110 TZIDC 120 42 18 84 EN ...
Page 77: ...Ex relevant specifications 42 18 84 EN TZIDC TZIDC 110 TZIDC 120 77 ...
Page 84: ...Appendix 84 TZIDC TZIDC 110 TZIDC 120 42 18 84 EN ...