background image

Operating instruction manual 

| TX Thermal Disperson Level Switches   5 

3.0  CALIBRATION / SET POINT PROCEDURE

Determining High and Low Thermal Conductivity Process conditions

I.  It is usually easy to recognize the high and low thermal conductivity conditions when the switch is applied to 

liquid and vapor conditions (high and low level detection).  The higher TC is almost always when the sensors are 

in the liquid phase.

II.  There are interface applications where the high and low TC process conditions may not be so obvious.

III.  The TX switch itself can be used to identify the high and low TC conditions.

A.   Remove power from the TX.

B.   Make connections to pins 1 and 3 of P2 (Pin 1 is nearest the green LED).

1.  Temporarily insert small pieces of solid wire in P1 or P2; or,

2.  Use ABB TX service plug connected to P1 on:  

a.  Main board (using gender changer adapter) for (single relay output); or,

b.  Piggy-back board (dual set point/output, without gender changer adaptor).

c.  Pin 1 is green wire; pin 3 is yellow wire on TX service plug.

C.   Connect a mV meter to Pin 1 (-) and pin 3 (+)

D.  Apply power to the TX.  The mV read will be due to the difference in temperature between the Active      

      Sensor and the Reference Sensor.

E.  Change the process conditions at the TX sensors from Normal to Alarm, allowing time to stabilize (5 

       minutes) and log these mV values.

1.  Higher mV value indicates LOW Thermal Conductivity at the sensors (heat is not being 

      conducted away as well from the Active sensor allowing the temperature of that sensor to 

       increase).

2.  Lower mV value indicates HIGH Thermal Conductivity at the sensors (heat is being conducted 

       away from the Active sensor, keeping the temperature at lower values.

3.1    Calibrate from HIGH TC (Thermal Conductivity) process conditions as follows:

JP3 State A 

 - Green LED, output relay 

energized

 at 

NORMAL

 condition (High Thermal Conductivity (low differential 

temperature) conditions at the sensors);  high level (level above sensor), flow above setpoint (see table page 6)

Notes:

1.  If the TX switch is operated in 

State A

, the TX switch should be adjusted (calibrated) in the 

NORMAL

 

condition; Highest Thermal Conductivity conditions on the sensors (wet sensor, high flow); Green LED and 

output relay will be energized during and after calibration.

2.  CW rotation of R18 turns LED ON.

Calibration Adjustments

  1. Provide the 

NORMAL

 condition (

HIGH

 Thermal Conductivity process condition (high level (level above the 

      sensors), high flow)) at the sensor.  Green LED and output relay 

will be

 energized after calibration.

  2. Allow 5 minutes (minimum time) for switch temperature to stabilize.

  3. Adjust R18 (drawing page 5) as follows:

a.   If LED is On – slowly turn R18 counter clockwise (CCW) to OFF.  Then turn CW until ON.

b.   If LED is Off – slowly turn R18 clockwise (CW) until green LED turns ON

  4. Turn R18 CW as follows for stable operation (no false alarms) (LED will be On):

a.   Air – 1 full turn

b.   Organics/Hydrocarbons – 2 full turns

c.   Water – 3 full turns

Trimming the TX settings for optimum alarm return to normal time balance if required:  

When the LED just turns ON, (3.b. above), the TX “alarm/recovery (return to normal) window” is positioned nearest 

to the process’s energized LED Normal (high TC; Low mV) value.  This provides the shortest possible time to recog

-

nize (enter) the de-energized alarm condition, but the longest possible recovery time back to the energized (normal) 

state.

Step 4 is an attempt to provide closer equal response times (time to enter alarm vs. time to recognize normal condi

-

tions and exit the alarm condition) as well as stability from false alarms.

Summary of Contents for TX series

Page 1: ...v J Flow level granular solids and temperature switch K TEK Products Introduction This operating instruction manual provides the following information Calibration set point procedure see page 5 Config...

Page 2: ...Level Operation 13 5 3 Installation for Flow Rates Minimum and Maximum 13 5 4 Installation for Remote Electronics 14 5 5 Installation Setup 15 6 0 Flow Rate Detection 16 7 0 INTERFACE DETECTION 16 8 0...

Page 3: ...against the probes the molecules of the medium absorb more heat from the active sensor and the voltage differential begins to drop or as the flow rate increases the voltage differential will decrease...

Page 4: ...ol system If fail safe is to be incorporated the output relay and green LED should be energized at what is determined as the normal condition JP3 jumpers are used to determine the relay action vs the...

Page 5: ...ower values 3 1 Calibrate from HIGH TC Thermal Conductivity process conditions as follows JP3 State A Green LED output relay energized at NORMAL condition High Thermal Conductivity low differential te...

Page 6: ...hermal Conductivity process condition high level level above sensor high flow condition at the sensor Green LED and output relay will be de energized after calibration adjust ments 2 Allow 5 minutes m...

Page 7: ...a combination of level and temperature or flow and temperature with the dual switch point option With the dual switch point option board the flow rate of a process can be monitored with the millivolt...

Page 8: ...witch set for Level or Air Flow Fail Safe High Level or High Flow JP3 Relay set for State B Energizes when dry or below flow set point above setting of R18 Two Jumpers x 2mm Switch set for Temperature...

Page 9: ...rgized LED On Fail Safe WET or Air Flow Set Point Normal Condition DRY or Air Flow Set Point Normal Condition Relay De energized LED OFF DRY or Air Flow Set Point Normal Condition WET or Air Flow Set...

Page 10: ...the delta voltage The output has an inverse relationship to flow and is not linear the output voltage decreases as flow increases The amplified output does not apply when used as a temperature switch...

Page 11: ...ation Condition State A State B Relay Energized LED On DRY or Air Flow Set Point WET or Air Flow Set Point Relay De energized LED OFF WET or Air Flow Set Point DRY or Flow Set Point LEVEL OR AIR FLOW...

Page 12: ...leg used to mount the instrument be the same as the instrument connec tion size 1 MNPT type The standard instrument 1 8 inch will fit in a 1 X 1 X 1 or larger tee The 1 2 inch option units are availa...

Page 13: ...and Maximum This switch can be also be configured to detect between a minimum or a maximum flow rate or a minimum maximum temperature With the dual circuit board option the unit can also detect a flow...

Page 14: ...perature that exceeds the maximum operating temperature 140 F or 65 C of the electronics module The remote housing simply contains a terminal block interface for a cable which connects to another hous...

Page 15: ...it in a tee the tee size should be the same size as the line or smaller A larger diameter tee will allow the water to expand and cause false trip to occur because of vortices and or eddy currents The...

Page 16: ...nse time is needed the TQ version may be the solution For small flow rates the IX or IM in line unit would be the option The delta voltage will decrease With the dual switch point top board the delta...

Page 17: ...40 50 60 70 80 90 300 275 4 297 9 320 3 342 7 365 387 4 409 6 431 8 450 476 2 200 498 3 520 4 542 4 564 4 586 3 608 2 630 1 651 9 673 7 695 5 100 717 2 738 8 760 5 782 1 803 6 825 1 846 6 868 0 889 4...

Page 18: ...del 141mV TQ Model 140mV TS Model 460mV IX Model 110mV Water TX HO Model 30mV H1 H2 Model 10mV TQ Model 25mV TS Model 90mV IX Model 15mV 9 2 1 With power disconnected measure resistance of Heater and...

Page 19: ...Operating instruction manual TX Thermal Disperson Level Switches 19 10 0 APPENDIX A Instrument Rangeability 10 1 TX Series 10 2 IX Series...

Page 20: ...vel Switches Operating instruction manual 11 0 APPENDIX B Conversion Table Examples Example 1 100 CFM in 4 line 100 x 1884 18 84 F P S Example 2 10 G P M in 3 line 10 x 0434 434 F P S Test Conditions...

Page 21: ...tion H1 320 F 500 F RED RED WHT BLK GRN SEE WIRE MARKERS Special Temperature Range Option H2 100 F 900 F TERMINAL NUMBER 1 2 3 4 5 HTR HTR ACT COM REF Integral Electronics RED RED YEL BLK GRN Remote E...

Page 22: ...3 0 APPENDIX D TX Heating vs Dispersion Above is a graph of the model TX probe The longer line depicts the time response of the RTD by internal heating The shorter line depicts the delta voltage or de...

Page 23: ...h were not the result of either alterations misuse abuse improper or inadequate adjustments applications or servicing of the product ABB s warranty does not include onsite repair or services Field ser...

Page 24: ...vel Switches Operating instruction manual 15 0 CUSTOMER SUPPORT ABB USA Canada International 18321 Swamp Road Prairieville LA 70769 USA Tel 1 225 673 6100 Fax 1 225 673 2525 Email service ktekcorp com...

Page 25: ...Data Sheets MSDS and decontamination tags by affixing these documents in close proximity to the shipment label for identification purposes January 18 2006 Return Authorization Form Customer Date Cont...

Page 26: ...26 TX Thermal Disperson Level Switches Operating instruction manual...

Page 27: ...Operating instruction manual TX Thermal Disperson Level Switches 27...

Page 28: ...ble lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilizatio...

Reviews: