background image

16   TX Thermal Disperson Level Switches | 

Operating instruction manual

6.0  FLOW RATE DETECTION

Configure circuit board jumpers JP3 (Relay State A) so the relay will be energized (green LED on) at the minimum flow 

rate then adjust as follows:

Allow the product to flow at the minimum rate for approximately three minutes. (This will allow the unit to establish 

an accurate flow set point and delta voltage.) 

The orientation of the probe is important to minimize the time to 

respond to a minimum flow rate.

 If the probe head is turned after adjustment, the unit will not respond correctly. 

Adjustment could be problematic due to the minimum torque required to the probe head and its orientation. The switch 

should never be installed near a bend in the pipe.

Adjust potentiometer (R18 on drawing p.7) on circuit board until green LED changes state as follows, at flow or at 

level:

• 

If LED is on - turn potentiometer counterclockwise

• 

If LED is off - turn potentiometer clockwise

Adjust the pot where the green LED is just on, this is the set-point. A flow rate greater than the minimum will keep the 

LED on and the relay energized. A flow rate less than the minimum will turn off the LED and de-energized the relay. In 

State B, the relay can be made to work so the LED is off above a flow rate. The hysteresis is about 10 mV. Moving JP3 

to (Relay State B) reverses the function of the relay and the LED. When the LED is on the relay is energized.

There is an inherent time delay that can not be compensated in a flow rate, interface or temperature application. The 

larger the difference in flow rates (minimum and maximum) the longer it will take the switch to respond. If a quicker 

response time is needed, the TQ version may be the solution. For small flow rates, the IX or IM (in line unit) would be 

the option. The delta voltage will decrease. With the dual switch point (top board) the delta voltage can be monitored 

and/or plotted to determine flow rate (inverse relationship and non-linear). The voltage output can not be used with 

temperature.

This switch can be configured to detect the interface between any two of the following mediums: granular solids (sand) 

and liquid (oil), foam and liquids, hydrocarbons (oil) and aqueous solutions (water), or whenever there is a unique 

seperation of product/s with reference to its thermal conductivity. The unit would likely be mounted horizontally (or 

vertically with an extended probe) and the insertion level of the switch would be the level of the interface. The board 

setting can be adjusted so the LED is ON or OFF (JP3/JP11 setting) when the interface is detected. Consult factory for 

options and settings in this application.

7.0  INTERFACE DETECTION

This switch can be configured to detect the interface between any two of the following mediums: granular solids (sand) 

and liquid (oil), foam and liquids, hydrocarbons (oil) and aqueous solutions (water), or whenever there is a unique 

separation of products with reference to thermal conductivity. The unit would likely be mounted horizontally (or verti

-

cally with an extended probe) and the insertion level of the switch would be at the level of the interface. The board 

setting can be adjusted so the LED is ON or OFF (JP3/JP11) when the interface is detected. 

1. 

Determine Normal Process Condition

2. 

Decide whether relay is energized or de-energized at normal conditions

3. 

Determine if T.C. (Thermal Conductivity) is high or low at normal conditions. Measure change in voltage (P2 pins 

1,3) - higher voltage is lower T.C.

4. 

Based on above data and choices, See section 3.1 or 3.2.

Summary of Contents for TX series

Page 1: ...v J Flow level granular solids and temperature switch K TEK Products Introduction This operating instruction manual provides the following information Calibration set point procedure see page 5 Config...

Page 2: ...Level Operation 13 5 3 Installation for Flow Rates Minimum and Maximum 13 5 4 Installation for Remote Electronics 14 5 5 Installation Setup 15 6 0 Flow Rate Detection 16 7 0 INTERFACE DETECTION 16 8 0...

Page 3: ...against the probes the molecules of the medium absorb more heat from the active sensor and the voltage differential begins to drop or as the flow rate increases the voltage differential will decrease...

Page 4: ...ol system If fail safe is to be incorporated the output relay and green LED should be energized at what is determined as the normal condition JP3 jumpers are used to determine the relay action vs the...

Page 5: ...ower values 3 1 Calibrate from HIGH TC Thermal Conductivity process conditions as follows JP3 State A Green LED output relay energized at NORMAL condition High Thermal Conductivity low differential te...

Page 6: ...hermal Conductivity process condition high level level above sensor high flow condition at the sensor Green LED and output relay will be de energized after calibration adjust ments 2 Allow 5 minutes m...

Page 7: ...a combination of level and temperature or flow and temperature with the dual switch point option With the dual switch point option board the flow rate of a process can be monitored with the millivolt...

Page 8: ...witch set for Level or Air Flow Fail Safe High Level or High Flow JP3 Relay set for State B Energizes when dry or below flow set point above setting of R18 Two Jumpers x 2mm Switch set for Temperature...

Page 9: ...rgized LED On Fail Safe WET or Air Flow Set Point Normal Condition DRY or Air Flow Set Point Normal Condition Relay De energized LED OFF DRY or Air Flow Set Point Normal Condition WET or Air Flow Set...

Page 10: ...the delta voltage The output has an inverse relationship to flow and is not linear the output voltage decreases as flow increases The amplified output does not apply when used as a temperature switch...

Page 11: ...ation Condition State A State B Relay Energized LED On DRY or Air Flow Set Point WET or Air Flow Set Point Relay De energized LED OFF WET or Air Flow Set Point DRY or Flow Set Point LEVEL OR AIR FLOW...

Page 12: ...leg used to mount the instrument be the same as the instrument connec tion size 1 MNPT type The standard instrument 1 8 inch will fit in a 1 X 1 X 1 or larger tee The 1 2 inch option units are availa...

Page 13: ...and Maximum This switch can be also be configured to detect between a minimum or a maximum flow rate or a minimum maximum temperature With the dual circuit board option the unit can also detect a flow...

Page 14: ...perature that exceeds the maximum operating temperature 140 F or 65 C of the electronics module The remote housing simply contains a terminal block interface for a cable which connects to another hous...

Page 15: ...it in a tee the tee size should be the same size as the line or smaller A larger diameter tee will allow the water to expand and cause false trip to occur because of vortices and or eddy currents The...

Page 16: ...nse time is needed the TQ version may be the solution For small flow rates the IX or IM in line unit would be the option The delta voltage will decrease With the dual switch point top board the delta...

Page 17: ...40 50 60 70 80 90 300 275 4 297 9 320 3 342 7 365 387 4 409 6 431 8 450 476 2 200 498 3 520 4 542 4 564 4 586 3 608 2 630 1 651 9 673 7 695 5 100 717 2 738 8 760 5 782 1 803 6 825 1 846 6 868 0 889 4...

Page 18: ...del 141mV TQ Model 140mV TS Model 460mV IX Model 110mV Water TX HO Model 30mV H1 H2 Model 10mV TQ Model 25mV TS Model 90mV IX Model 15mV 9 2 1 With power disconnected measure resistance of Heater and...

Page 19: ...Operating instruction manual TX Thermal Disperson Level Switches 19 10 0 APPENDIX A Instrument Rangeability 10 1 TX Series 10 2 IX Series...

Page 20: ...vel Switches Operating instruction manual 11 0 APPENDIX B Conversion Table Examples Example 1 100 CFM in 4 line 100 x 1884 18 84 F P S Example 2 10 G P M in 3 line 10 x 0434 434 F P S Test Conditions...

Page 21: ...tion H1 320 F 500 F RED RED WHT BLK GRN SEE WIRE MARKERS Special Temperature Range Option H2 100 F 900 F TERMINAL NUMBER 1 2 3 4 5 HTR HTR ACT COM REF Integral Electronics RED RED YEL BLK GRN Remote E...

Page 22: ...3 0 APPENDIX D TX Heating vs Dispersion Above is a graph of the model TX probe The longer line depicts the time response of the RTD by internal heating The shorter line depicts the delta voltage or de...

Page 23: ...h were not the result of either alterations misuse abuse improper or inadequate adjustments applications or servicing of the product ABB s warranty does not include onsite repair or services Field ser...

Page 24: ...vel Switches Operating instruction manual 15 0 CUSTOMER SUPPORT ABB USA Canada International 18321 Swamp Road Prairieville LA 70769 USA Tel 1 225 673 6100 Fax 1 225 673 2525 Email service ktekcorp com...

Page 25: ...Data Sheets MSDS and decontamination tags by affixing these documents in close proximity to the shipment label for identification purposes January 18 2006 Return Authorization Form Customer Date Cont...

Page 26: ...26 TX Thermal Disperson Level Switches Operating instruction manual...

Page 27: ...Operating instruction manual TX Thermal Disperson Level Switches 27...

Page 28: ...ble lack of information in this document We reserve all rights in this document and in the subject matter and illustrations contained therein Any reproduction disclosure to third parties or utilizatio...

Reviews: